Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2032189
Status: Active
Facility Name: Circle J's Shell
Address: 641 North Roselle Road Roselle, IL 60172
County: Du Page
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002824
Green Tag Issue Date: 2/15/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: O J's Oil Enterprises, Ltd.
Owner Address: 641 N. Roselle Rd. Roselle, IL 60172
Owner Status: Current Owner
Purchase Date: 4/1/2011
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 10/7/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 2/15/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0036347 O J's Oil Enterprises, Ltd. Current Owner 4/1/2011
U0031959 Shaan Food, Inc. Former Owner 8/1/2003
U0029011 BK Oil Corp Former Owner 8/31/1999
U0021676 Roselle Rd Partners Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251653 (Pending)    Issue Date: 7/1/2025    Expiration Date: 8/30/2025    View NOV Form

Tanks Violations
4 Dispensers - hoses cracked, split or worn and require replacement - Replace main hoses. Dispenser #15 has slight leak at breakaway and nozzle. Dispenser #16 has slight leak at nozzle. All leaks shall be repaired when main hoses are replaced.
1, 2, 3, 4 Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps.
1, 2, 3, 4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.
1, 2, 3, 4 Tank monitor does not appear to function properly and requires maintenance. - Yellow warning light not working. Repair bulb.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/28/1994 Abandoned Material:
Current Age: 41 Abandoned Date:
Install Date: 1/1/1994 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1984

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/20/2025 3/20/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/20/2025 3/20/2026
Overfill Prev Device Overfill Drop Tube Valve 3/20/2025 3/20/2028
Piping Flexible Double Wall NUPI Smartflex N/A N/A
Piping Single Wall STP/Tanktop Sump 3/20/2025 3/20/2028
Leak Detect - Piping Sump Sensor 3/20/2025 3/20/2026
Spill Contain Device Double Wall Spill Bucket 3/20/2025 3/20/2028
Tank Composite Double Wall Permatank N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall NUPI Smartflex Precision Test (Piping) Pass 3/20/2025



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Ultra Low Sulfur Diesel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/28/1994 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: 1/1/1994 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1994

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/20/2025 3/20/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/20/2025 3/20/2026
Overfill Prev Device Overfill Drop Tube Valve 3/20/2025 3/20/2028
Piping Flexible Double Wall NUPI Smartflex N/A N/A
Piping Single Wall STP/Tanktop Sump 3/20/2025 3/20/2028
Leak Detect - Piping Sump Sensor 3/20/2025 3/20/2026
Spill Contain Device Double Wall Spill Bucket 3/20/2025 3/20/2028
Tank Composite Double Wall Permatank N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall NUPI Smartflex Precision Test (Piping) Pass 3/20/2025



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/28/1994 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: 1/1/1994 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1994

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/20/2025 3/20/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/20/2025 3/20/2026
Overfill Prev Device Overfill Drop Tube Valve 3/20/2025 3/20/2028
Piping Flexible Double Wall NUPI Smartflex N/A N/A
Piping Single Wall STP/Tanktop Sump 3/20/2025 3/20/2028
Leak Detect - Piping Sump Sensor 3/20/2025 3/20/2026
Spill Contain Device Double Wall Spill Bucket 3/20/2025 3/20/2028
Tank Composite Double Wall Permatank N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall NUPI Smartflex Precision Test (Piping) Pass 3/20/2025



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/8/2001 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 1/18/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/20/2025 3/20/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/20/2025 3/20/2026
Overfill Prev Device Overfill Drop Tube Valve 3/20/2025 3/20/2028
Piping Flexible Double Wall NUPI Smartflex N/A N/A
Piping Single Wall STP/Tanktop Sump 3/20/2025 3/20/2028
Leak Detect - Piping Sump Sensor 3/20/2025 3/20/2026
Spill Contain Device Double Wall Spill Bucket 3/20/2025 3/20/2028
Tank Fiberglass Double Wall Owens Corning N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall NUPI Smartflex Precision Test (Piping) Pass 3/20/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/20/2025 3/20/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/20/2025 3/20/2026



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/20/2025 3/20/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/20/2025 3/20/2026



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/20/2025 3/20/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/20/2025 3/20/2026



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/20/2025 3/20/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/20/2025 3/20/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/20/2025 3/20/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/20/2025 3/20/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/20/2025 3/20/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/20/2025 3/20/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/20/2025 3/20/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/20/2025 3/20/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/20/2025 3/20/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/20/2025 3/20/2026

MFD Motorfuel Dispensing Forms

No Forms Found