Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2031790
Status: Active
Facility Name: Thornton's #115
Address: 800 Northwest Highway Cary, IL 60013
County: McHenry
Property Parcel: 19-11-276-005
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001388
Green Tag Issue Date: 2/21/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Thorntons, LLC
Owner Address: 2600 James Thornton Way Louisville, KY 40245
Owner Status: Current Owner
Purchase Date: 2/11/2019
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 1/9/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039521 Thorntons, LLC Current Owner 2/11/2019
U0014995 Thornton's, Inc. - DO NOT USE THIS OWNER ID Former Owner 8/31/2006

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260975 (Pending)    Issue Date: 4/13/2026    Expiration Date: 6/12/2026    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers.

NOV Number: E0020260976 (Pending)    Issue Date: 4/13/2026    Expiration Date: 6/12/2026    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - 2026 (ESTOP) ELECTRICAL SHUTOFF SWITCHES TEST IS NOT IN THE COMPLIANCE BINDER, DID SEE 2025. All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain most current 2 years on site with other annual testing documentation.
Facility Facility Operation and Maintenance Plan not completed or available. - Adopt and implement a written operations and maintenance plan, signed by both the owner and either a Class A or Class B Operator designated for the UST facility An Operations & Maintenance template is available at www.sfm.illinois.gov to download and complete O & M template and maintain completed form on site.
Facility Missing copies of Annual Walkthrough Inspection Report. - 2026 ANNUAL WALKTHROUGH INSPECTION IS NOT IN THE COMPLIANCE BINDER, DID SEE 2025.Annual Walkthrough by a licensed contractor shall be conducted and most current 2 years documentation maintained on site.
Facility Missing copies of current testing certificates for operator training - WAS ONLY ABLE TO SEE MANAGERS "C" CERTIFICATE, AND MAGGIE SEABAUGH'S "AB" CERT, NO OTHER CERTS IN THE BOOK, MUST HAVE AB CERT FOR AB OPERATOR CONDUCTING 30 DAY WALKTHROUGH. Copies of all current Class A/B testing certificates shall be maintained on file on site. Copies of all current Class C testing certificates shall be maintained on file on site.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures plan shall be maintained on site for viewing and reference as necessary (See Operator Training Rules 176.645). The emergency plan template is available on the OSFM website.
Facility Missing list of designated Class A/B & C Operators
6, 7, 8, 9, 10 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - 2026 SHEAR VALVE INSPECTION IS NOT IN THE COMPLIANCE BINDER, DID SEE 2025. Provide documentation that annual testing of all shear valves has been conducted and passed. Must maintain most current 2 years of inspection reports.
6, 7, 8, 9, 10 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
06-0616 5/22/2006 Removal Log 01312-2005REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
06-0616 Eligible 11/6/2006 11/6/2006 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/22/2006
OSFM First Notify Date: 7/16/1993 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 5/16/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/17/1993

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/22/2006
OSFM First Notify Date: 7/16/1993 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 5/16/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/17/1993

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/22/2006
OSFM First Notify Date: 7/16/1993 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 5/16/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/17/1993

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/22/2006
OSFM First Notify Date: 7/16/1993 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 5/16/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/17/1993

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 6000 Petroleum Use:
Product: Kerosene CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/22/2006
OSFM First Notify Date: 7/16/1993 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 5/16/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/17/1993

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/31/2006 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 6/9/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/9/2006

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/20/2026 2/20/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 2/20/2026 2/20/2027
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 2/25/2025 2/25/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 12/16/2025 12/16/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/20/2026 2/20/2027
Spill Contain Device Double Wall Spill Bucket 3/17/2026 3/17/2029
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Pisces Precision Test (Piping) Pass 5/26/2023
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 8/9/2020



Tank Number 7

Capacity: 10000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/31/2006 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 6/9/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/9/2006

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/20/2026 2/20/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 2/20/2026 2/20/2027
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 2/25/2025 2/25/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 12/16/2025 12/16/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/20/2026 2/20/2027
Spill Contain Device Double Wall Spill Bucket 3/17/2026 3/17/2029
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 8

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/31/2006 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 6/9/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/9/2006

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/20/2026 2/20/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 2/20/2026 2/20/2027
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 2/25/2025 2/25/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 12/16/2025 12/16/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/20/2026 2/20/2027
Spill Contain Device Double Wall Spill Bucket 3/17/2026 3/17/2029
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 9

Capacity: 14000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/31/2006 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 6/9/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/9/2006

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/20/2026 2/20/2027
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 2/20/2026 2/20/2027
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 2/25/2025 2/25/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 12/16/2025 12/16/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/20/2026 2/20/2027
Spill Contain Device Double Wall Spill Bucket 3/17/2026 3/17/2029
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping Siphon Bar Functional Pass 2/28/2019



Tank Number 10

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/31/2006 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 6/9/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/9/2006

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/20/2026 2/20/2027
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 2/20/2026 2/20/2027
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 2/25/2025 2/25/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 12/16/2025 12/16/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/20/2026 2/20/2027
Spill Contain Device Double Wall Spill Bucket 3/17/2026 3/17/2029
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping Siphon Bar Functional Pass 2/28/2019

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/16/2025 12/16/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/20/2026 2/20/2027



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/16/2025 12/16/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/20/2026 2/20/2027



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/16/2025 12/16/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/20/2026 2/20/2027



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/16/2025 12/16/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/20/2026 2/20/2027



Name\ID 17/18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/16/2025 12/16/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/20/2026 2/20/2027



Name\ID 19/20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/16/2025 12/16/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/20/2026 2/20/2027



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/16/2025 12/16/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/20/2026 2/20/2027



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/16/2025 12/16/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/20/2026 2/20/2027



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/16/2025 12/16/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/20/2026 2/20/2027



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/16/2025 12/16/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/20/2026 2/20/2027

MFD Motorfuel Dispensing Forms