Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2031596
Status: Active
Facility Name: Mainstream Pumping Station
Address: 6100 South River Road
Hodgkins, IL 60525
County: Cook
Property Parcel:
Facility Type: Utility
Owner Type: Private
Green Tag Decal: Z003472
Green Tag Issue Date: 9/12/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Metropolitan Water Reclamation District of Greater Chicago (MWRDGC)
Owner Address: 100 E. Erie Street
Chicago, IL 60611
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 6/29/2026

Motor Fuel Dispensing Permits

No MFD Permits Found

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0010188 Metropolitan Water Reclamation District of Greater Chicago (MWRDGC) Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

No Notice of Violations Found

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 7000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/1/1992 Abandoned Material:
Current Age: 39 Abandoned Date:
Install Date: 11/20/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 8/12/2024 8/12/2025
Corrosion Prot - Tank Impressed Current Cathodic Protection 8/12/2024 8/12/2025
Leak Detect - Piping American with Annual Prec Line Testing Suction 5/23/2018 5/23/2019
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300c with CSLD 8/12/2024 8/12/2025
Overfill Prev Device Overfill Alarm 8/12/2024 8/12/2027
Piping Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 8/12/2024 8/12/2027
Tank Steel Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping American with Annual Prec Line Testing Suction Functional Pass 8/12/2024
Piping Steel Single Wall Piping Precision Test (Piping) Pass 8/12/2024
Tank Steel Single Wall Precision Test (Tank) Pass 8/12/2024



Tank Number 2

Capacity: 1500 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/1/1992 Abandoned Material:
Current Age: 39 Abandoned Date:
Install Date: 11/20/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 8/12/2024 8/12/2025
Corrosion Prot - Tank Impressed Current Cathodic Protection 8/12/2024 8/12/2025
Leak Detect - Piping American with Annual Prec Line Testing Suction 5/23/2018 5/23/2019
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300c with CSLD 8/12/2024 8/12/2025
Overfill Prev Device Overfill Alarm 8/12/2024 8/12/2027
Piping Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 8/12/2024 8/12/2027
Tank Steel Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping American with Annual Prec Line Testing Suction Functional Pass 8/12/2024
Piping Steel Single Wall Piping Precision Test (Piping) Pass 8/12/2024
Tank Steel Single Wall Precision Test (Tank) Pass 8/12/2024

Dispenser Information



MFD Motorfuel Dispensing Forms

No Forms Found