Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2031373
Status: Active
Facility Name: Transportation Dept.
Address: 500 Shales Parkway Elgin, IL 60120
County: Kane
Property Parcel: 00000000
Facility Type: School/College
Owner Type: Other Local
Green Tag Decal: Z003748
Green Tag Issue Date: 2/27/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: School District U-46
Owner Address: 355 E. Chicago st. Elgin, IL 60120
Owner Status: Current Owner
Purchase Date: 3/17/1992
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 3/3/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 2/27/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0017351 School District U-46 Current Owner 3/17/1992

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252123 (Pending)    Issue Date: 8/18/2025    Expiration Date: 10/17/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain 2 years on site with other annual testing documentation.
1 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
1 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
2 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
2 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
3 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
3 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
4 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
4 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site.
1, 2, 3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Must maintain 2 years of inspection reports.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Diesel Fuel Currently in use Federal $0.00
2 10000 Diesel Fuel Currently in use Federal $0.00
3 10000 Diesel Fuel Currently in use Federal $0.00
4 1000 Used Oil Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1 Active
2 Active
3 Active
4 Active
5 Active
6 Active
7 Active
8 Active

MFD Motorfuel Dispensing Forms

No Forms Found