Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2030001
Status: Active
Facility Name: Circle K #6743
Address: 1805 Belvidere Road
Grayslake, IL 60030
County: Lake
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001221
Green Tag Issue Date: 3/7/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: RDK Ventures, LLC
Owner Address: 1120 W. Warner Rd.
Tempe, AZ 85284
Owner Status: Current Owner
Purchase Date: 1/7/2010
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/24/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/7/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures, LLC Current Owner 1/7/2010
U0027449 Equilon Enterprises, LLC Former Owner 6/1/1992
U0013849 Shell Oil Products Former Owner 12/31/1967
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020251009 (Pending)    Issue Date: 4/15/2025    Expiration Date: 6/14/2025    View NOV Form

Tanks Violation
1, 2, 3 Line interstitial sensors have been raised and rendered inoperational. - (STP/UDC) Interstitial sensor(s) are not functioning effectively. Place sensors vertically at the lowest point in the sump. (Per Ill Adm. Code 175.410.l.2.A.ii)
2 Open electrical conduit or junction boxes. - Electrical conduit in STP containment is corroded and wires are exposed.
2 Triennial spill prevention equipment testing not completed.
2 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - STP containment requires testing.
1, 2, 3 Water in dispenser containment with interstitial sensors - Remove water and repair containments to prevent water ingress - Fuel in UDC (disp 5/6), investigate and repair.

NOV Number: E0020251010 (Pending)    Issue Date: 4/15/2025    Expiration Date: 6/14/2025    View NOV Form

Tanks Violation
Facility Dispensers require collision protection - Bollards are corroded Provide appropriate collision protection for above referenced dispenser island(s). (Per Ill Adm. Code 175.450.e.13)

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
03-0507 Eligible 5/7/2003 5/23/2003 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/24/1993 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: 6/10/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/13/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/1/2025 4/1/2026
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 4/1/2025 4/1/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 4/1/2025 4/1/2026
Overfill Prev Device Overfill Drop Tube Valve 6/5/2024 6/5/2027
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 4/17/2024 4/17/2027
Leak Detect - Piping Sump Sensor 4/1/2025 4/1/2026
Spill Contain Device Single Wall Spill Bucket 4/17/2024 4/17/2027
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 4/1/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors Sensor Functional Pass 4/10/2008
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 4/10/2008



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/24/1993 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: 6/10/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/13/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Other Non-vented check valve N/A N/A
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 4/1/2025 4/1/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 4/1/2025 4/1/2026
Overfill Prev Device Overfill Drop Tube Valve 6/5/2024 6/5/2027
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 5/4/2021 5/4/2024
Leak Detect - Piping Non-Discriminating Sump Sensor 6/1/2022 6/1/2023
Leak Detect - Piping Sump Sensor with positive shutdown 4/1/2025 4/1/2026
Spill Contain Device Single Wall Spill Bucket 5/4/2021 5/4/2024
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 4/1/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors Sensor Functional Pass 4/10/2008
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 4/10/2008



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/24/1993 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: 6/10/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/13/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/1/2025 4/1/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 4/1/2025 4/1/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 4/1/2025 4/1/2026
Overfill Prev Device Overfill Drop Tube Valve 6/5/2024 6/5/2027
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 4/17/2024 4/17/2027
Leak Detect - Piping Sump Sensor 4/1/2025 4/1/2026
Spill Contain Device Single Wall Spill Bucket 4/17/2024 4/17/2027
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 4/1/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors Sensor Functional Pass 4/10/2008
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 4/10/2008

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/16/2024 9/16/2027
Leak Detect - Piping Stand Alone Sump Sensor 4/1/2025 4/1/2026



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/17/2024 4/17/2027
Leak Detect - Piping Stand Alone Sump Sensor 4/1/2025 4/1/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/17/2024 4/17/2027
Leak Detect - Piping Stand Alone Sump Sensor 4/1/2025 4/1/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/17/2024 4/17/2027
Leak Detect - Piping Stand Alone Sump Sensor 4/1/2025 4/1/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/16/2024 9/16/2027
Leak Detect - Piping Stand Alone Sump Sensor 4/1/2025 4/1/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/16/2024 9/16/2027
Leak Detect - Piping Stand Alone Sump Sensor 4/1/2025 4/1/2026

MFD Motorfuel Dispensing Forms

No Forms Found