Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0041136 |
590 Lake Properties, LLC |
Current Owner |
12/1/2023 |
| U0036745 |
Lake & Spring Amoco, Inc. |
Former Owner |
12/10/2012 |
| U0032360 |
Angel Associates, LP |
Former Owner |
12/14/2009 |
| U0027493 |
Amoco Oil Company |
Former Owner |
1/1/1983 |
| U0000552 |
BP Products North America, Inc. |
Former Owner |
1/1/1983 |
| U0000574 |
Amoco Oil Company |
Former Owner |
12/31/1967 |
| U0038389 |
Lake BP, Inc. |
Former Owner |
|
Notice of Violations (Current)
NOV Number:
E0020261738
(Pending)
Issue Date:
5/19/2026
Expiration Date:
7/18/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Facility Operation and Maintenance Plan not completed or available. - Operations and Maintenance Template needs to be updated and kept on site. https://sfm.illinois.gov/ |
| Facility |
Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures Plan needs to be updated and kept on site. https://sfm.illinois.gov/ |
| 1, 2, 3 |
Tank monitor does not appear to function properly and requires maintenance. - ATG is in alarm W1 WPLLD Com Alarm. Repair so ATG is clear of alarms. |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/13/1991 |
|
Abandoned Material: |
|
| Current Age: |
43 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1983 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1983 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Cathodic Protection |
10/18/2024 |
10/18/2027 |
|
Corrosion Prot - Tank
|
Sacrificial Anode Cathodic Protection |
10/18/2024 |
10/18/2027 |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
1/4/2026 |
1/4/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
1/4/2026 |
1/4/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
11/20/2025 |
11/20/2028 |
|
Piping
|
Steel Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
10/20/2025 |
10/20/2028 |
|
Tank
|
STIP3 Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Steel Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
5/18/2024
|
|
Tank
|
STIP3 Single Wall
|
Precision Test (Tank)
|
Pass
|
5/18/2024
|
Tank Number 2
| Capacity: |
10000 |
|
Petroleum Use: |
Dispensing |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/13/1991 |
|
Abandoned Material: |
|
| Current Age: |
43 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1983 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1983 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Cathodic Protection |
10/18/2024 |
10/18/2027 |
|
Corrosion Prot - Tank
|
Sacrificial Anode Cathodic Protection |
10/18/2024 |
10/18/2027 |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
1/4/2026 |
1/4/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
1/4/2026 |
1/4/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
11/20/2025 |
11/20/2028 |
|
Piping
|
Steel Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
10/20/2025 |
10/20/2028 |
|
Tank
|
STIP3 Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Steel Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
5/18/2024
|
|
Tank
|
STIP3 Single Wall
|
Precision Test (Tank)
|
Pass
|
5/18/2024
|
Tank Number 3
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/13/1991 |
|
Abandoned Material: |
|
| Current Age: |
43 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1983 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1983 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Cathodic Protection |
10/18/2024 |
10/18/2027 |
|
Corrosion Prot - Tank
|
Sacrificial Anode Cathodic Protection |
10/18/2024 |
10/18/2027 |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
1/4/2026 |
1/4/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
1/4/2026 |
1/4/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
11/20/2025 |
11/20/2028 |
|
Piping
|
Steel Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
11/20/2025 |
11/20/2028 |
|
Tank
|
STIP3 Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Steel Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
5/18/2024
|
Tank Number 4
| Capacity: |
15000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Does Not Exist |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
|
|
Abandoned Material: |
|
| Current Age: |
|
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
No passing test found |
No passing test found |
|
Leak Detect - Piping
|
Sump Sensor |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Hydrostatic Reservoir Interstitial Monitoring Sensors |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Ball Float Vent Valve OPW 30MV |
No passing test found |
No passing test found |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Fiberglass Brine Filled Double Wall Containment Solutions |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 5
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Does Not Exist |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
|
|
Abandoned Material: |
|
| Current Age: |
|
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
No passing test found |
No passing test found |
|
Leak Detect - Piping
|
Sump Sensor |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Hydrostatic Reservoir Interstitial Monitoring Sensors |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Ball Float Vent Valve OPW 30MV |
No passing test found |
No passing test found |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Fiberglass Brine Filled Double Wall Containment Solutions |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 6
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Does Not Exist |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
|
|
Abandoned Material: |
|
| Current Age: |
|
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
No passing test found |
No passing test found |
|
Leak Detect - Piping
|
Sump Sensor |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Hydrostatic Reservoir Interstitial Monitoring Sensors |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Ball Float Vent Valve OPW 30MV |
No passing test found |
No passing test found |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Fiberglass Brine Filled Double Wall Containment Solutions |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 7
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Does Not Exist |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
|
|
Abandoned Material: |
|
| Current Age: |
|
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
No passing test found |
No passing test found |
|
Leak Detect - Piping
|
Sump Sensor |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Hydrostatic Reservoir Interstitial Monitoring Sensors |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Ball Float Vent Valve OPW 30MV |
No passing test found |
No passing test found |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Fiberglass Brine Filled Double Wall Containment Solutions |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 5/6
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 7/8
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found