Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2027464
Status: Active
Facility Name: JM Food Shop, Inc.
Address: 11200 South Vine Street Huntley, IL 60142
County: McHenry
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001672
Green Tag Issue Date: 3/31/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: JM Food Shop, Inc.
Owner Address: 11200 South Vine Street Huntley, IL 60142
Owner Status: Current Owner
Purchase Date: 8/25/2015
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 6/30/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/2/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037997 JM Food Shop, Inc. Current Owner 8/25/2015
U0032164 FDH Baki, LLC Former Owner 11/1/2002
U0000916 Athans Co. Partnership Former Owner 12/5/1989

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251682 (Pending)    Issue Date: 7/3/2025    Expiration Date: 9/1/2025    View NOV Form

Tanks Violations
Facility A/B operator retraining required as a result of issuance of the Notice of Violation - Primary A / B certified operator shall be retrained as a result of this NOV being issued.
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain 2 years on site with other annual testing documentation.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site.
Facility Missing copies of current testing certificates for operator training - Copies of all current Class C testing certificates shall be maintained on file on site.
Facility Missing list of designated Class A/B & C Operators - A comprehensive list of Class A / B / C Operator(s) shall be maintained on site and must be current. LIST NOT MAINTAINED OR CURRENT
1, 2, 3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Must maintain 2 years of inspection reports.

NOV Number: E0020251683 (Pending)    Issue Date: 7/3/2025    Expiration Date: 9/1/2025    View NOV Form

Tanks Violations
Facility Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - Section 175.210g; All dispensing units shall be readily visible from the control station without assistive devices. If view is permanently obstructed, or the dispenser is located so that activity is not readily visible, closed-circuit cameras that provide a view of each side of the dispensing unit and project an image on a screen at least 6 inches in diagonal located at the control station may be used. You may also elect to install an emergency stop switch at least 20 feet but no more than 50 feet from any dispenser with a permanently obstructed view.
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers.
Facility LP gas storage lacks proper collision protection or a 40" measurement from cabinet to a 5" raised sidewalk - Provide appropriate collision protection for LP tank cage. Refer to OSFM Rules section 175.210 q) for proper placement of collision protection.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Diesel Fuel Currently in use Federal $0.00
2 10000 Gasoline - Premium Currently in use Federal $0.00
3 10000 Gasoline - Regular Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active

MFD Motorfuel Dispensing Forms