4, 5, 6 |
Line interstitial sensors have been raised and rendered inoperational. - Dispenser 3/4
175.640 a) 2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump. |
5 |
Line leak detection equipment in alarm or failed test, must repair or replace. - Tank 5 STP sump sensor failed annual testing. Repair or replace sensor and enter passing results on OSFM portal. |
5 |
Miscellaneous - Vapor adaptor is broken on drop tube. |
6 |
Miscellaneous - Premium vapor cap is broken. |
7 |
Miscellaneous - ATG shows 8 gallons .97" of water in tank. |
4, 5, 6, 7 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to
the environment when the transfer hose is detached from the fill
pipe (e.g., a spill catch basin). Spill containment equipment shall
be maintained in a dry, clean state. |
4, 5, 6, 7 |
Tank monitor does not appear to function properly and requires maintenance. - Green indicator light is out. Repair so light is lit. |
4, 5, 6 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Dispenser 3/4 |