Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2027372
Status: Active
Facility Name: IL0091
Address: 1200 N. Rand Rd. Wauconda, IL 60084
County: Lake
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000787
Green Tag Issue Date: 6/13/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Lehigh Gas Wholesale Services Inc.
Owner Address: 645 Hamilton, Suite 400 Allentown, PA 18101
Owner Status: Current Owner
Purchase Date: 9/27/2016
Type of Financial Responsibility: Surety Bond
Financial Responsibility Reporting Due Date: 4/14/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037337 Lehigh Gas Wholesale Services Inc. Current Owner 9/27/2016
U0000651 B.A.P.A., LLC & PT, LLC Former Owner 10/23/2014
U0032738 Shree Gi Krupa Corporation Former Owner 9/5/2003
U0029789 Clark Retail Enterprises, Inc. Former Owner 7/8/1999
U0003073 Clark Retail Enterprises, Inc. Former Owner 10/25/1994
U0014487 S & S Petroleum Former Owner 12/31/1967
U0025164 BAPA, LLC & PT, LLC Former Owner
U0028787 Clark Retail Enterprises, Inc., Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260924 (Pending)    Issue Date: 4/8/2026    Expiration Date: 6/7/2026    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2, 3 Line interstitial sensors have been raised and rendered inoperational. - (STP/UDC) Interstitial sensor(s) are not functioning effectively. Place sensors vertically at the lowest point in the sump. (Per Ill Adm. Code 175.410(l)(2)(A)(ii))
3 Line leak detection equipment in alarm or failed test, must repair or replace. - Electronic line leak detector would not detect leak during annual testing.
Facility Missing copies of Annual Walkthrough Inspection Report.
1, 2, 3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
16-0580 8/26/2016 Abandonment Log 00817-2016ABN

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
94-0117 Eligible 5/6/2015 5/13/2015 $10,000
16-0580 Eligible 11/2/2016 11/4/2016 $5,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/26/1990 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/2/2026 4/2/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 4/2/2026 4/2/2027
Overfill Prev Device Overfill Drop Tube Valve 4/2/2026 4/2/2029
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 10/23/2024 10/23/2027
Leak Detect - Piping Sump Sensor 4/2/2026 4/2/2027
Spill Contain Device Double Wall Spill Bucket 5/9/2024 5/9/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 4/2/2026



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/26/1990 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/2/2026 4/2/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 4/2/2026 4/2/2027
Overfill Prev Device Overfill Drop Tube Valve 4/2/2026 4/2/2029
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 10/23/2024 10/23/2027
Leak Detect - Piping Sump Sensor 4/2/2026 4/2/2027
Spill Contain Device Double Wall Spill Bucket 5/9/2024 5/9/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 4/2/2026



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/26/1990 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/9/2026 4/9/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 4/2/2026 4/2/2027
Overfill Prev Device Overfill Drop Tube Valve 4/2/2026 4/2/2029
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Double Wall STP/Tanktop Sump 10/23/2024 10/23/2027
Leak Detect - Piping Sump Sensor 4/2/2026 4/2/2027
Spill Contain Device Double Wall Spill Bucket 5/9/2024 5/9/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 4/2/2026



Tank Number 4

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Abandoned in place CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/26/1990 Abandoned Material: Inert material mixed with portland cement
Current Age: 36 Abandoned Date: 8/26/2016
Install Date: Red Tag Issue Date:
Last Used Date: 3/31/2016 Fee Due: $0.00
Product Date: 12/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 2/16/2016 2/16/2017
Corrosion Prot - Piping Sacrificial Anode Flex Connector 2/13/2014 2/13/2017
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/16/2016 2/16/2017
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Single Wall Piping N/A N/A
Piping Steel Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/23/2024 10/23/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/2/2026 4/2/2027



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/23/2024 10/23/2027
Leak Detect - Piping Sump Sensor 4/2/2026 4/2/2027



Name\ID 13-14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/23/2024 10/23/2027
Leak Detect - Piping Sump Sensor 4/2/2026 4/2/2027



Name\ID 15-16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/23/2024 10/23/2027
Leak Detect - Piping Sump Sensor 4/2/2026 4/2/2027



Name\ID 17

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/23/2024 10/23/2027
Leak Detect - Piping Sump Sensor 4/2/2026 4/2/2027



Name\ID 17 S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/23/2024 10/23/2027
Leak Detect - Piping Sump Sensor 4/2/2026 4/2/2027



Name\ID 18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/23/2024 10/23/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/2/2026 4/2/2027



Name\ID 18 S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/23/2024 10/23/2027
Leak Detect - Piping Sump Sensor 4/2/2026 4/2/2027



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/23/2024 10/23/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/2/2026 4/2/2027



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/23/2024 10/23/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/2/2026 4/2/2027



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/23/2024 10/23/2027
Leak Detect - Piping Sump Sensor 4/2/2026 4/2/2027



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/23/2024 10/23/2027
Leak Detect - Piping Sump Sensor 4/2/2026 4/2/2027

MFD Motorfuel Dispensing Forms

No Forms Found