Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2026853
Status: Active
Facility Name: WLS Radio Transmitter Site
Address: 18301 White Eagle Drive Tinley Park, IL 60487
County: Cook
Property Parcel:
Facility Type: Federal (Non-Military)
Owner Type: Federal
Green Tag Decal: Z002653
Green Tag Issue Date: 11/26/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: FEMA
Owner Address: 5 NW 0408500 500 C St. South West Washington, DC 20472
Owner Status: Current Owner / Operator
Purchase Date:
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 7/1/2026

Motor Fuel Dispensing Permits

No MFD Permits Found

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0022431 FEMA Current Owner / Operator
U0016955 Wls Am Inc Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
01100-2025REM Removal Approved / Issued 8/21/2025 8/21/2025 2/23/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020252027 (Pending)    Issue Date: 8/11/2025    Expiration Date: 10/10/2025    View NOV Form

Tanks Violations
3, 4 Annual leak detection certification not completed (Required annually). - (ATG Cert.)
3, 4 Line interstitial sensor functional test not accomplished (Required annually).
3, 4 Tank interstitial sensor functional test not accomplished (Required annually).

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
91-0974 4/11/1991 Removal Log

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 5760 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 4/11/1991
OSFM First Notify Date: 3/12/1991 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 1/1/1978 Red Tag Issue Date:
Last Used Date: 9/1/1978 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 550 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 4/11/1991
OSFM First Notify Date: 4/9/1991 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 12/1/1977 Red Tag Issue Date:
Last Used Date: 4/1/1991 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 5000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/16/1993 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 4/10/1991 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date: 4/11/1991

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Composite Secondary Containment N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping American with Sensors/No Test Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Incon TS 550 EVO 8/6/2024 8/6/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/6/2024 8/6/2025
Overfill Prev Device Overfill Drop Tube Valve 8/6/2024 8/6/2027
Piping Aboveground N/A N/A
Piping Polyethylene Chase N/A N/A
Piping Copper Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump 8/18/2022 8/18/2025
Leak Detect - Piping Sump Sensor 8/6/2024 8/6/2025
Spill Contain Device Single Wall Spill Bucket 8/6/2024 8/6/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping American with Annual Prec Line Testing Suction Functional Pass 8/15/2018
Leak Detect - Piping American with Annual Prec Line Testing Suction Functional Pass 8/13/2021
Leak Detect - Piping American with Sensors/No Test Suction Functional Pass 8/6/2024
Leak Detect - Piping American with Sensors/No Test Suction Functional Pass 8/13/2021
Piping Chase Secondary Containment steel primary within composite secondary Precision Test (Piping) Pass 8/18/2022
Piping Copper Single Wall Piping Precision Test (Piping) Pass 8/6/2024
Piping Polyethylene Chase Precision Test (Piping) Pass 8/10/2023
Tank Composite Double Wall Modern Welding Glasteel II Precision Test (Tank) Pass 8/1/2019



Tank Number 4

Capacity: 6000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/16/1993 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 4/10/1991 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date: 4/11/1991

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Composite Secondary Containment N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping American with Sensors/No Test Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Incon TS 550 EVO 8/6/2024 8/6/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/6/2024 8/6/2025
Overfill Prev Device Overfill Drop Tube Valve 8/6/2024 8/6/2027
Piping Aboveground N/A N/A
Piping Polyethylene Chase N/A N/A
Piping Copper Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump 8/18/2022 8/18/2025
Leak Detect - Piping Sump Sensor 8/6/2024 8/6/2025
Spill Contain Device Single Wall Spill Bucket 8/6/2024 8/6/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping American with Annual Prec Line Testing Suction Functional Pass 8/15/2018
Leak Detect - Piping American with Annual Prec Line Testing Suction Functional Pass 8/13/2021
Leak Detect - Piping American with Sensors/No Test Suction Functional Pass 8/13/2021
Leak Detect - Piping American with Sensors/No Test Suction Functional Pass 8/6/2024
Piping Chase Secondary Containment steel primary within composite secondary Precision Test (Piping) Pass 8/18/2022
Piping Copper Single Wall Piping Precision Test (Piping) Pass 8/6/2024
Piping Polyethylene Chase Precision Test (Piping) Pass 8/10/2023
Tank Composite Double Wall Modern Welding Glasteel II Precision Test (Tank) Pass 8/1/2019

Dispenser Information



MFD Motorfuel Dispensing Forms

No Forms Found