Notice of Violatlions (Current)
NOV Number:
E0020260764
(Pending)
Issue Date:
3/24/2026
Expiration Date:
5/23/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Installed but not working. Feedback on the speaker. |
NOV Number:
E0020260775
(Pending)
Issue Date:
3/24/2026
Expiration Date:
5/23/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Financial responsibility must be reported yearly |
| Facility |
Submit Notification Form for Facility Information Change - Facility Name Change |
| 5 |
Tank precision test required. - Regular Tank East has a high water alarm. Facility has tank shut down. |
| 5 |
Triennial spill prevention equipment testing not completed. - Have contractor input the date of the hydro test when they tested the new spill bucket at install |