Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2025864
Status: Active
Facility Name: Brake Time
Address: 103 N. Ridge Road Minooka, IL 60447
County: Grundy
Property Parcel: 03-02-200-020
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: AA03946
Green Tag Issue Date: 1/12/2026
Green Tag Expiration Date: 12/31/2027

Owner Details

Owner Name: Brake Time IL Properties, LLC
Owner Address: 6300 Richmond Avenue, Suite 300 Houston, TX 77057
Owner Status: Current Owner
Purchase Date: 11/6/2024
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 10/27/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/12/2026 12/31/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041353 Brake Time IL Properties, LLC Current Owner 11/6/2024
U0041353 Brake Time IL Properties, LLC Former Owner 11/5/2024
U0039389 Minit Mart, LLC Former Owner 12/5/2018
U0026726 TA Operating, LLC Former Owner 8/13/2015
U0010459 MKM Oil, Inc. Former Owner 1/3/1990

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260072 (Pending)    Issue Date: 1/12/2026    Expiration Date: 3/13/2026    View NOV Form

Tanks Violations
1, 3 Flex connector sacrificial anode system not tested (required every 3 years) - Test anodes and replace as needed - 175.510 f)2)A)i) Sacrificial anodes shall be tested every 3 years as long as testing results are -850 millivolts or a higher negative number. In the event testing results do not meet the -850 millivolt requirement, the anodes shall be replaced. This requirement applies to all sacrificial anodes, including wristband and spike anodes.
1, 2, 3 Tank sacrificial anode system not tested (Required every 3 years). - 175.510 f)2)A)i) Sacrificial anodes shall be tested every 3 years as long as testing results are -850 millivolts or a higher negative number. In the event testing results do not meet the -850 millivolt requirement, the anodes shall be replaced. This requirement applies to all sacrificial anodes, including wristband and spike anodes.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/18/1990 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 3/6/1990 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/6/1990

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 12/5/2022 12/5/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 12/5/2022 12/5/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/16/2025 9/16/2026
Leak Detect - Tank Automatic Tank Gauging Red Jacket Pro Max with CSLD 9/16/2025 9/16/2026
Overfill Prev Device Overfill Drop Tube Valve 12/6/2024 12/6/2027
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 12/6/2024 12/6/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 9/30/2024



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/18/1990 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 3/6/1990 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/6/1990

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 12/5/2022 12/5/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/16/2025 9/16/2026
Leak Detect - Tank Automatic Tank Gauging Red Jacket Pro Max with CSLD 9/16/2025 9/16/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 12/6/2024 12/6/2027
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 12/6/2024 12/6/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 9/30/2024



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/18/1990 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 3/6/1990 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/6/1990

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 12/5/2022 12/5/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 12/5/2022 12/5/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/16/2025 9/16/2026
Leak Detect - Tank Automatic Tank Gauging Red Jacket Pro Max with CSLD 9/16/2025 9/16/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 12/27/2024 12/27/2027
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 12/6/2024 12/6/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 9/30/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found