Notice of Violatlions (Current)
NOV Number:
E0020260072
(Pending)
Issue Date:
1/12/2026
Expiration Date:
3/13/2026
View NOV Form
| Tanks |
Violations |
| 1, 3 |
Flex connector sacrificial anode system not tested (required every 3 years) - Test anodes and replace as needed - 175.510 f)2)A)i) Sacrificial anodes shall be tested every 3 years as long as
testing results are -850 millivolts or a higher negative
number. In the event testing results do not meet the -850
millivolt requirement, the anodes shall be replaced. This
requirement applies to all sacrificial anodes, including
wristband and spike anodes. |
| 1, 2, 3 |
Tank sacrificial anode system not tested (Required every 3 years). - 175.510 f)2)A)i) Sacrificial anodes shall be tested every 3 years as long as
testing results are -850 millivolts or a higher negative
number. In the event testing results do not meet the -850
millivolt requirement, the anodes shall be replaced. This
requirement applies to all sacrificial anodes, including
wristband and spike anodes. |