Notice of Violatlions (Current)
NOV Number:
E0020252702
(Pending)
Issue Date:
10/9/2025
Expiration Date:
12/8/2025
View NOV Form
Tanks |
Violations |
7, 8, 9, 10, 11 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Triennial inspection of overfill device (drop tube valve or overfill alarm) has not been completed. Testing shall be completed and submitted to OSFM with passing results. |
6, 7, 8, 9, 10, 11 |
Piping interstitial must be open in all sumps - Remove schrader valves or cut testing tubes to open double wall piping. (All UDC's) |
6, 7, 8, 9, 10 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill Bucket(s) contain(s) liquid and/or debris; remove liquid/debris and maintain clean and dry at all times. |
7, 9 |
Triennial spill prevention equipment testing not completed. - Triennial inspection/testing of spill bucket(s) has not been completed. Testing shall be completed with passing results. |
NOV Number:
E0020252703
(Pending)
Issue Date:
10/9/2025
Expiration Date:
12/8/2025
View NOV Form
Tanks |
Violations |
Facility |
Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - Cameras-- closed-circuit cameras that provide a view of each side of the dispensing unit and project an image on a screen at least 6 inches in diagonal located at the control station. Reference 175.210 g) |
Facility |
Dispenser control device wiring does not comply with NFPA 70 (1996) Chapter 5 - There is wire hanging in the dispenser. |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Truck stop side does not work. |