Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2025256
Status: Active
Facility Name: L & B Business Enterprises, LLC
Address: 3001 W. Belmont Ave. Chicago, IL 60618
County: Cook
Property Parcel: 13-25-102-016-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z002366
Green Tag Issue Date: 3/8/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: L & B Business Enterprises, LLC
Owner Address: 8060 N. Lawndale Skokie, IL 60076
Owner Status: Current Owner
Purchase Date: 8/28/2015
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 3/14/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035877 L & B Business Enterprises, LLC Current Owner 8/28/2015
U0035189 PAV 2, LLC, Former Owner 10/31/2014
U0029977 B & S Service Station Inc Former Owner 1/31/2001
U0004928 F&O Ser Inc Former Owner 3/8/1996

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00299-2026UPG Upgrade Approved / Issued 3/17/2026 3/18/2026 9/18/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020260589 (Pending)    Issue Date: 3/6/2026    Expiration Date: 5/5/2026    View NOV Form

Tanks Violations
1, 2, 3, 5 Annual electronic line leak detector test not completed.
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2, 3, 5 Annual leak detection certification not completed (Required annually).
Facility Electrical Does Not Comply - Regular ELD open connection and Premium Junction box for sump missing cover.
Facility Financial responsibility must be reported yearly - https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility
2 Flex connector damaged or worn - replace flex connector and precision test line - Premium sump has gas in from probable leaking flex line. Failing .2 gal/hr line tests.
1, 2, 3, 5 Line interstitial sensor functional test not accomplished (Required annually). - E-85 dispenser, Sump, and tank
2, 5 Line leak detection equipment in alarm or failed test, must repair or replace. - E-85 Sensor in alarm for tank interstitial. Periodic line fail for Premium Gasoline
Facility Missing copies of Annual Walkthrough Inspection Report.
1, 2, 3, 5 Overfill prevention equipment inspection(s) not completed (Required every 3 years).
1, 2, 3, 5 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
5 Tank interstitial sensor functional test not accomplished (Required annually).
1 Tank monitor does not appear to function properly and requires maintenance. - Tank #1 Probe Out Alarm.
1, 2, 3, 5 Triennial spill prevention equipment testing not completed.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
02-1747 12/4/2002 Removal Log 107153

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
14-1328 Eligible 12/4/2014 1/16/2015 $5,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Gasoline - Premium Currently in use Federal $0.00
3 8000 Diesel Fuel Currently in use Federal $0.00
4 500 Used Oil Removed Federal $0.00 12/04/2002 - REM
5 6000 E85 Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
2025256 L & B Business Enterprises, LLC Chicago 06/02/2023 Letter Form