| 1, 2, 3, 5 |
Annual electronic line leak detector test not completed. |
| Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. |
| 1, 2, 3, 5 |
Annual leak detection certification not completed (Required annually). |
| Facility |
Electrical Does Not Comply - Regular ELD open connection and Premium Junction box for sump missing cover. |
| Facility |
Financial responsibility must be reported yearly - https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility |
| 2 |
Flex connector damaged or worn - replace flex connector and precision test line - Premium sump has gas in from probable leaking flex line. Failing .2 gal/hr line tests. |
| 1, 2, 3, 5 |
Line interstitial sensor functional test not accomplished (Required annually). - E-85 dispenser, Sump, and tank |
| 2, 5 |
Line leak detection equipment in alarm or failed test, must repair or replace. - E-85 Sensor in alarm for tank interstitial. Periodic line fail for Premium Gasoline |
| Facility |
Missing copies of Annual Walkthrough Inspection Report. |
| 1, 2, 3, 5 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). |
| 1, 2, 3, 5 |
Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). |
| 5 |
Tank interstitial sensor functional test not accomplished (Required annually). |
| 1 |
Tank monitor does not appear to function properly and requires maintenance. - Tank #1 Probe Out Alarm. |
| 1, 2, 3, 5 |
Triennial spill prevention equipment testing not completed. |