Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0040674 |
908 Streamwood, LLC |
Current Owner |
9/6/2022 |
| U0039984 |
CGV Real Estate, LLC |
Former Owner |
5/1/2020 |
| U0034093 |
Esquire Petroleum, LLC |
Former Owner |
5/1/2011 |
| U0031788 |
Garcia, Orestes |
Former Owner |
8/7/2003 |
| U0000103 |
A M Petroleum Inc |
Former Owner |
|
Notice of Violations (Current)
NOV Number:
E0020261421
(Pending)
Issue Date:
6/2/2026
Expiration Date:
8/1/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. - Copies must be kept on site |
| 5, 6, 7 |
Line leak detection equipment in alarm or failed test, must repair or replace. - Premium tank top STP sump sensor in alarm |
| Facility |
Missing copies of Annual Walkthrough Inspection Report. - Copies must be kept on site |
| Facility |
Missing copies of current testing certificates for operator training - Copies must be kept on site |
| 5, 6, 7 |
Monthly line interstitial sensor records not available. |
| 5, 6, 7 |
Required monthly tank interstitial sensor records not available. |
| 5, 6, 7 |
Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Copies must be kept on site |
| 5, 6, 7 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
NOV Number:
E0020261427
(Pending)
Issue Date:
6/2/2026
Expiration Date:
8/1/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Miscellaneous - Each emergency stop shall be identified by a sign stating "EMERGENCY STOP" in 2 inch red capital letters. 175.210.d.3 |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
6/20/1991 |
|
OSFM
First Notify Date: |
1/26/1990 |
|
Abandoned Material: |
|
| Current Age: |
29 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
3/1/1990 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
6/20/1991 |
|
OSFM
First Notify Date: |
1/26/1990 |
|
Abandoned Material: |
|
| Current Age: |
29 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
3/1/1990 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
6/20/1991 |
|
OSFM
First Notify Date: |
1/26/1990 |
|
Abandoned Material: |
|
| Current Age: |
29 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
3/1/1990 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 4
| Capacity: |
4000 |
|
Petroleum Use: |
None |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
6/20/1991 |
|
OSFM
First Notify Date: |
1/26/1990 |
|
Abandoned Material: |
|
| Current Age: |
29 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
3/1/1990 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 5
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/19/2003 |
|
Abandoned Material: |
|
| Current Age: |
22 |
|
Abandoned Date: |
|
| Install Date: |
8/8/2003 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
11/20/2003 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
11/11/2025 |
11/11/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
11/11/2025 |
11/11/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
1/6/2026 |
1/6/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
10/24/2024 |
10/24/2027 |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
10/24/2024 |
10/24/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
10/24/2024 |
10/24/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
10/24/2024 |
10/24/2027 |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 6
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
E85 |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/19/2003 |
|
Abandoned Material: |
|
| Current Age: |
22 |
|
Abandoned Date: |
|
| Install Date: |
8/8/2003 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
11/20/2003 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
11/11/2025 |
11/11/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
11/11/2025 |
11/11/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
11/11/2025 |
11/11/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
10/24/2024 |
10/24/2027 |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
10/24/2024 |
10/24/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
10/24/2024 |
10/24/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
10/24/2024 |
10/24/2027 |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall Environ Geo Flex
|
Precision Test (Piping)
|
Pass
|
10/31/2023
|
Tank Number 7
| Capacity: |
4000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/19/2003 |
|
Abandoned Material: |
|
| Current Age: |
22 |
|
Abandoned Date: |
|
| Install Date: |
8/8/2003 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
11/20/2003 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
11/11/2025 |
11/11/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
11/11/2025 |
11/11/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
11/11/2025 |
11/11/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
10/24/2024 |
10/24/2027 |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
10/24/2024 |
10/24/2027 |
Leak Detect - Piping
|
Sump Sensor |
10/24/2024 |
10/24/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
10/24/2024 |
10/24/2027 |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
10/24/2024
|
10/24/2027
|
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
11/11/2025
|
11/11/2026
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
10/24/2024
|
10/24/2027
|
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
11/11/2025
|
11/11/2026
|
Name\ID 5/6
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
10/24/2024
|
10/24/2027
|
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
11/11/2025
|
11/11/2026
|
Name\ID 7/8
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
10/24/2024
|
10/24/2027
|
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
11/11/2025
|
11/11/2026
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found