Notice of Violatlions (Current)
NOV Number:
E0020252102
(Referred to Legal)
Issue Date:
8/14/2025
Expiration Date:
10/13/2025
View NOV Form
| Tanks |
Violations |
| 1 |
Annual leak detection certification not completed (Required annually). - Annual leak detection testing shall be performed and passing results entered on OSFM portal. |
| 1 |
Sacrificial system failed test; must repair. - 175.510 f)2)A)i) Sacrificial anodes shall be tested every 3 years as long as
testing results are -850 millivolts or a higher negative
number. In the event testing results do not meet the -850
millivolt requirement, the anodes shall be replaced. This
requirement applies to all sacrificial anodes, including
wristband and spike anodes. |
NOV Number:
E0020260147
(Pending)
Issue Date:
1/21/2026
Expiration Date:
3/22/2026
View NOV Form
| Tanks |
Violations |
| 1 |
Failed to Empty the Tank to 1" or Less |
| 1 |
Submit Notification Form For Tank Status Change - The Notification Form is available at: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of a tank status change. |