Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2024544
Status: Active
Facility Name: Libertyville Mobil
Address: 1185 W. Park Avenue Libertyville, IL 60048
County: Lake
Property Parcel: 11-20-200-004
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000737
Green Tag Issue Date: 3/20/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Butterpark Real Estate Inc.
Owner Address: 1185 W Park Ave. Libertyville, IL 60048
Owner Status: Current Owner
Purchase Date: 12/2/2025
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 2/20/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041736 Butterpark Real Estate Inc. Current Owner 12/2/2025
U0002560 Casey's Retail Company Former Owner 5/14/2021
U0036013 Buchanan Energy (N), LLC Former Owner 12/9/2010
U0010471 ExxonMobil Oil Corporation Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260417 (Pending)    Issue Date: 2/23/2026    Expiration Date: 4/24/2026    View NOV Form

Tanks Violations
1, 2, 3, 4 Annual electronic line leak detector test not completed.
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2, 3, 4 Annual leak detection certification not completed (Required annually).
1, 2, 3, 4 Line interstitial sensor functional test not accomplished (Required annually).
3 Line interstitial sensors have been raised and rendered inoperational. - (STP) Interstitial sensor(s) are not functioning effectively. Place sensors vertically at the lowest point in the sump. (Per Ill Adm. Code 175.410(l)(2)(A)(ii))
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom.
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures plan shall be maintained on site for viewing and reference as necessary (See Operator Training Rules 176.645). The emergency plan template is available on the OSFM website.
Facility Missing list of designated Class A/B & C Operators
1, 2, 3, 4 Monthly line interstitial sensor records not available. - Maintain one NORMAL/PASS report per LINE, per month, from ATG. (Liquid Status)
Facility Operations & Maintenance plan missing required frequencies - Adopt and implement a written operations and maintenance plan, signed by both the owner and either a Class A or Class B Operator designated for the UST facility An Operations & Maintenance template is available at www.sfm.illinois.gov to download and complete O & M template and maintain completed form on site.
1, 2, 3, 4 Overfill prevention equipment inspection(s) not completed (Required every 3 years).
1, 2, 3, 4 Precision line test required. - Precision line test is required (Per 41 Ill Admin code 175.640(a)(4))
1, 2, 3, 4 Required monthly tank leak test records not available. - Maintain one NORMAL/PASS report per TANK, per month, from tank monitor. (CSLD)
1, 2, 3, 4 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
1, 2, 3, 4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1, 2, 3, 4 Tank precision test required. - Precision tank test is required due to missing or failed monthly monitoring (Per 41 Ill Admin code 175.630(c)(2))
1, 2, 3, 4 Triennial spill prevention equipment testing not completed.
1, 2, 3, 4 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Missing STP & UDC triannual testing.
2 Vent cap(s) missing.
3 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP sump(s) contain(s) liquid. Remove liquid and repair containment to prevent further liquid ingress. Must show documentaion showing repairs completed. (Per 41 Ill Admin code 175.410(h))

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
02-0606 5/30/2002 Removal Log 00374-2002REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
88-1189 Eligible 8/5/1994 8/24/1994 $50,000
02-0606 Ineligible 3/25/2005 4/25/2005 $Not Selected
88-1189 Eligible 6/27/2011 8/24/2011 $50,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 12000 Gasoline - Regular Currently in use Federal $0.00
2 12000 Gasoline - Regular Currently in use Federal $0.00
3 12000 Gasoline - Regular Currently in use Federal $0.00
4 12000 Gasoline - Premium Currently in use Federal $0.00
5 10000 Gasoline Removed Federal $0.00 08/01/1988 - REM
6 10000 Gasoline Removed Federal $0.00 08/01/1988 - REM
7 10000 Gasoline Removed Federal $0.00 08/01/1988 - REM
8 1000 Gasoline Removed Exempt 05/30/2002 - REM
9 560 Gasoline Removed Exempt 05/30/2002 - REM
10 1000 Gasoline Removed Exempt 05/30/2002 - REM

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
9/10 Active
11/12 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found