Deficiencies (Current)
NOV Number:
E0020240825
(Pending)
Issue Date:
3/19/2024
Expiration Date:
6/7/2024
View NOV Form
Tanks |
Deficiency |
6, 8, 9 |
Line interstitial sensors have been raised and rendered inoperational. - All dispenser and Premium STP. |
Facility |
Missing list of designated Class A/B & C Operators - Form is available at https://sfm.illinois.gov to download and complete. Maintain documentation on site. |
6, 8, 9 |
Piping interstitial must be open in all sumps - Dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. 175.420 b) |
6, 8, 9 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Dispenser sumps 1-8 and 11/12. |
NOV Number:
E0020241648
(Pending)
Issue Date:
6/12/2024
Expiration Date:
8/11/2024
View NOV Form
Tanks |
Deficiency |
6, 8, 9 |
Miscellaneous - Sensors must be programmed for positive shutdown and verified. |