A/B operator retraining required as a result of issuance of the Notice of Violation |
Facility |
Due to a red tagged tank(s) at this facility, after 60 days from the issuance date of this NOV, in the absence of full compliance, all tanks shall be red tagged |
10 |
Kerosene dispensers must be located on a separate island and at least 20' away from other dispensers - Kerosene dispense is less than 20 feet from gasoline dispenser and on same island. Either Kerosene dispenser needs to be moved or gasoline dispenser needs to be removed. |
12, 13, 14 |
Perform a site assessment - IEMA #H2021-1062 |
12, 13, 14 |
Piping sacrificial anode system not tested (required every 3 years). - Piping was not cathodically protected as required. Piping appears to be single wall steel piping and not fiberglass as identified. Records show that the piping was not cathodically protected since last tested in March 2009. The piping must be replaced. |
10, 11, 12, 13, 14 |
Required monthly tank leak test records not available. - Need two years of passing Veeder Root Tank Records. |
10, 11, 12, 13, 14 |
Tank monitor does not appear to function properly and requires maintenance. - CSLD that was installed on Veeder Root is not functioning. Need to repait Veeder Root. |
14 |
The Blended Fuel Compatibility Form for products greater than E10 and B20 has not been submitted as required. |