Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2023209
Status: Active
Facility Name: BP AM-PM
Address: 700 East Route 45 Mundelein, IL 60060
County: Lake
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000781
Green Tag Issue Date: 5/28/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: SBA Petroleum, Inc.
Owner Address: 7345 Waterury Dr. Round Lake, IL 60073
Owner Status: Current Owner
Purchase Date: 10/18/2007
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 10/15/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/28/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0034454 SBA Petroleum, Inc. Current Owner 10/18/2007
U0023834 BP Amoco Former Owner 1/1/1993
U0000552 BP Products North America, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260064 (Pending)    Issue Date: 1/9/2026    Expiration Date: 3/10/2026    View NOV Form

Tanks Violations
10 Dispensers - hoses cracked, split or worn and require replacement
8, 9, 10, 11 Monthly line interstitial sensor records not available. - Failed monthly monitoring. Line interstitial sensors in alarm continously for over 12 months. L13 (Reg Fill): Liquid Warning L14 (Prem Fill): Fuel Alarm L17 (E85 STP): Fuel Alarm L18 (Diesel STP): Fuel Alarm
8, 9, 10, 11 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Tanks 8 and 9 missing ball float testing Tanks 10 and 11 missing overfill drop tube valve testing.
8, 9, 10, 11 Precision line test required. - Precision line test is required (Per 41 Ill Admin code 175.640(a)(4))
8, 9, 10, 11 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
8, 9, 10, 11 Tank monitor does not appear to function properly and requires maintenance. - Green and red indicator lights are not functioning.
8, 9, 10, 11 Triennial spill prevention equipment testing not completed.
8, 9, 10, 11 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - All containment sumps require testing.
8, 9, 10, 11 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP sump(s) contain(s) liquid. Remove liquid and repair containment to prevent further liquid ingress. Must show documentaion showing repairs completed. (Per 41 Ill Admin code 175.410(h))

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
04-1440 10/18/2004 Removal Log 04927-2004REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
90-3594 Eligible 6/7/1994 6/28/1994 $10,000
04-1440 Eligible 1/24/2005 2/2/2005 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 6000 Gasoline Removed Federal $0.00 08/01/1993 - REM
2 6000 Gasoline Removed Federal $0.00 08/01/1993 - REM
3 8000 Gasoline Removed Federal $0.00 08/01/1993 - REM
4 10000 Gasoline Removed Federal $0.00 08/01/1993 - REM
5 12000 Gasoline Removed Federal $0.00 10/18/2004 - REM
6 12000 Gasoline Removed Federal $0.00 10/18/2004 - REM
7 12000 Gasoline Removed Federal $0.00 10/18/2004 - REM
8 15000 Gasoline - Premium Currently in use Federal $0.00
9 20000 Gasoline - Regular Currently in use Federal $0.00
10 6000 B-11 Currently in use Federal $0.00
11 4000 E85 Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active
13/14 Active
15/16 Active
17/18 Active
19/20 Active

MFD Motorfuel Dispensing Forms

No Forms Found