Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2023169
Status: Active
Facility Name: Mobil Gas Station
Address: 2418 St. Charles Road Bellwood, IL 60104
County: Cook
Property Parcel: 15-10-121-047-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000058
Green Tag Issue Date: 5/29/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: BWood Corp.
Owner Address: 840 Huber Lane Glenview, IL 60025
Owner Status: Current Owner
Purchase Date: 4/19/2011
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 11/3/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0036776 BWood Corp. Current Owner 4/19/2011
U0033352 K J Oil Corporation Former Owner 12/28/2004
U0027493 Amoco Oil Company Former Owner 1/1/1988
U0000552 BP Products North America, Inc. Former Owner 1/1/1988
U0030549 Chandy, Joseph Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260665 (Pending)    Issue Date: 3/12/2026    Expiration Date: 5/11/2026    View NOV Form

Tanks Violations
6, 7 Dispensers - hoses cracked, split or worn and require replacement
6, 7 Line leak detection equipment in alarm or failed test, must repair or replace. - Veeder root showing alarm for WPLLD comm alarm
Facility Missing copies of 30 day Walkthrough Inspection Report.
6, 7 Shear valve(s) not properly mounted and/or not at proper height.
5, 6, 7 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

NOV Number: E0020260666 (Pending)    Issue Date: 3/12/2026    Expiration Date: 5/11/2026    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 500 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/1/1988
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 1/1/1976 Red Tag Issue Date:
Last Used Date: 8/1/1988 Fee Due: $0.00
Product Date: 1/1/1976

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/1/1988
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: 1/1/1961 Red Tag Issue Date:
Last Used Date: 8/1/1988 Fee Due: $0.00
Product Date: 1/1/1961

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/1/1988
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: 1/1/1961 Red Tag Issue Date:
Last Used Date: 8/1/1988 Fee Due: $0.00
Product Date: 1/1/1961

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/1/1988
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 1/1/1970 Red Tag Issue Date:
Last Used Date: 8/1/1988 Fee Due: $0.00
Product Date: 1/1/1970

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/26/1988 Abandoned Material:
Current Age: 38 Abandoned Date:
Install Date: 1/1/1988 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 1/28/2026 1/28/2027
Corrosion Prot - Tank Impressed Current Cathodic Protection 1/28/2026 1/28/2027
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/28/2026 1/28/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root EMC with CSLD 1/28/2026 1/28/2027
Overfill Prev Device Overfill Drop Tube Valve 12/4/2024 12/4/2027
Piping Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 12/4/2024 12/4/2027
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Steel Single Wall Piping Precision Test (Piping) Pass 1/28/2026
Tank STIP3 Single Wall Precision Test (Tank) Pass 5/15/2024



Tank Number 6

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/26/1988 Abandoned Material:
Current Age: 38 Abandoned Date:
Install Date: 1/1/1988 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 1/28/2026 1/28/2027
Corrosion Prot - Tank Impressed Current Cathodic Protection 1/28/2026 1/28/2027
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/28/2026 1/28/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root EMC with CSLD 1/28/2026 1/28/2027
Overfill Prev Device Overfill Drop Tube Valve 12/4/2024 12/4/2027
Piping Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 12/4/2024 12/4/2027
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Steel Single Wall Piping Precision Test (Piping) Pass 1/28/2026
Tank STIP3 Single Wall Precision Test (Tank) Pass 5/15/2024



Tank Number 7

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/26/1988 Abandoned Material:
Current Age: 38 Abandoned Date:
Install Date: 1/1/1988 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 1/28/2026 1/28/2027
Corrosion Prot - Tank Impressed Current Cathodic Protection 1/28/2026 1/28/2027
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/28/2026 1/28/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root EMC with CSLD 1/28/2026 1/28/2027
Overfill Prev Device Overfill Drop Tube Valve 12/4/2024 12/4/2027
Piping Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 12/4/2024 12/4/2027
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Steel Single Wall Piping Precision Test (Piping) Pass 1/28/2026
Tank STIP3 Single Wall Precision Test (Tank) Pass 5/15/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms