Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2023158
Status: Active
Facility Name: Round Lake BP
Address: 320 Nippersink Road Round Lake, IL 60073
County: Lake
Property Parcel: 06-29-107-011
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: AA00922
Green Tag Issue Date: 7/15/2025
Green Tag Expire Date: 12/31/2027
MFD Type: Self Service

Owner Details

Owner Name: Stone Enterprises Round Lake, LLC
Owner Address: 320 Nippersink Road Round Lake, IL 60073
Owner Status: Current Owner
Purchase Date: 8/17/2015
Type of Financial Responsibility: Letter of Credit
Financial Responsibility Reporting Due Date: 9/30/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037934 Stone Enterprises Round Lake, LLC Current Owner 8/17/2015
U0036765 Illini Petroleum, Inc. Former Owner 12/31/2012
U0027493 Amoco Oil Company Former Owner 1/1/1990
U0000552 BP Products North America, Inc. Former Owner 1/1/1990
U0023084 Graham Enterprise, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260966 (Pending)    Issue Date: 4/9/2026    Expiration Date: 6/8/2026    View NOV Form

Tanks Violations
7 Line leak detection equipment in alarm or failed test, must repair or replace. - Diesel leak detector FAILS 4/7/2026. "Diesel Leak detector FAILS to see 3.0 gph leak when tested." Diesel leak detector replaced under Like for Like 2/18/2026. "not functional" Diesel leak detector previously failed 4/22/2025. "Diesel PLLd fails; there is too much air in the line for the leak detector to sense the leak." Diesel leak detector previously failed 6/2/2020. "the leak detector does not function properly … does not shut down for a 3.0 gph leak" Diesel leak detector replaced under Like for Like 1/17/2020. Diesel leak detector previously failed 7/25/2019. "Did not see a 3.0 GPH leak" Diesel leak detector previously failed 6/12/2019. "too much air in the line and did not see a 3GPH leak" Diesel leak detector previously failed 6/19/2018 "Diesel leak detector fails to see 3.0 gph leak when tested. Diesel leak detector previously failed 1/4/2017 "The Diesel electronic line leak detector fails; it does not sense a 3 gph leak or shut down the line"

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
90-1960 7/13/1990 Removal Log

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
90-1960 Eligible 9/17/1996 10/11/1996 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 500 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/1/1990
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 7/1/1990 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/1/1990
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 7/1/1990 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/1/1990
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 7/1/1990 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/1/1990
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 7/1/1990 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/30/1996 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: 1/1/1990 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1990

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 4/7/2026 4/7/2027
Corrosion Prot - Tank Impressed Current Cathodic Protection 4/7/2026 4/7/2027
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/7/2026 4/7/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R 4/7/2026 4/7/2027
Overfill Prev Device Overfill Drop Tube Valve 4/22/2025 4/22/2028
Piping Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 4/3/2024 4/3/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Steel Single Wall Piping Precision Test (Piping) Pass 4/3/2024



Tank Number 6

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/30/1996 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: 1/1/1990 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1990

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 4/7/2026 4/7/2027
Corrosion Prot - Tank Impressed Current Cathodic Protection 4/7/2026 4/7/2027
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/7/2026 4/7/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R 4/7/2026 4/7/2027
Overfill Prev Device Overfill Drop Tube Valve 4/22/2025 4/22/2028
Piping Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 4/3/2024 4/3/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Steel Single Wall Piping Precision Test (Piping) Pass 4/3/2024



Tank Number 7

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/30/1996 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: 1/1/1990 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1990

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 4/7/2026 4/7/2027
Corrosion Prot - Tank Impressed Current Cathodic Protection 4/7/2026 4/7/2027
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/15/2026 5/15/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R 4/7/2026 4/7/2027
Overfill Prev Device Overfill Drop Tube Valve 4/22/2025 4/22/2028
Piping Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 4/3/2024 4/3/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Steel Single Wall Piping Precision Test (Piping) Pass 6/30/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms