Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2023093
Status: Active
Facility Name: Fuller's Gas & Quick Lube
Address: 5620 South Brainard Avenue Countryside, IL 60525
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000601
Green Tag Issue Date: 12/4/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Walter Fuller
Owner Address:
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 11/19/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0032586 Fuller, Walter Current Owner
U0000552 BP Products North America, Inc. Former Owner 5/19/1994
U0023834 BP Amoco Former Owner 6/13/1969
U0000565 Amoco Oil Co Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020261069 (Pending)    Issue Date: 4/21/2026    Expiration Date: 6/20/2026    View NOV Form

Tanks Violations
8, 9 Annual electronic line leak detector test not completed.
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
7, 8, 9 Annual leak detection certification not completed (Required annually).
Facility Facility Operation and Maintenance Plan not completed or available.
7, 8, 9 Line interstitial sensor functional test not accomplished (Required annually).
Facility Missing copies of 30 day Walkthrough Inspection Report.
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copies of current testing certificates for operator training
Facility Missing copy of emergency instructions or emergency procedures plan
Facility Missing list of designated Class A/B & C Operators
7, 8, 9 Monthly line interstitial sensor records not available. - PLEASE LOCATE THE LAST 2 YEARS
7, 8, 9 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - LAST TESTED ON 6-30-22
7, 8, 9 Required monthly tank interstitial sensor records not available. - PLEASE LOCATE THE LAST 2 YEARS OR TIGHTNESS TEST TANKS
7, 8, 9 Required monthly tank leak test records not available. - PLEASE SUBMIT THE LAST 2 YEARS OR TIGHTNESS TEST TANKS
7, 8, 9 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
7, 8, 9 Tank interstitial sensor functional test not accomplished (Required annually).

NOV Number: E0020261070 (Pending)    Issue Date: 4/21/2026    Expiration Date: 6/20/2026    View NOV Form

Tanks Violations
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - PLEASE REPLACE FADED SIGNS

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
89-0545 Eligible 5/27/1994 6/14/1994 $50,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 550 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 6/23/1989
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 6/23/1989 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/30/1993
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 1/1/1970 Red Tag Issue Date:
Last Used Date: 5/1/1992 Fee Due: $0.00
Product Date: 1/1/1970

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/30/1993
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 1/1/1970 Red Tag Issue Date:
Last Used Date: 5/1/1992 Fee Due: $0.00
Product Date: 1/1/1970

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/30/1993
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 1/1/1970 Red Tag Issue Date:
Last Used Date: 5/1/1992 Fee Due: $0.00
Product Date: 1/1/1970

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/30/1993
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 1/1/1970 Red Tag Issue Date:
Last Used Date: 5/1/1992 Fee Due: $0.00
Product Date: 1/1/1970

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 550 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/30/1993
OSFM First Notify Date: 6/5/1989 Abandoned Material:
Current Age: 3 Abandoned Date:
Install Date: 8/3/1989 Red Tag Issue Date:
Last Used Date: 5/1/1992 Fee Due: $0.00
Product Date: 8/3/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 7

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/7/2005 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 5/20/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/29/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/16/2026 2/16/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 10/22/2024 10/22/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 10/22/2024 10/22/2025
Overfill Prev Device Overfill Drop Tube Valve 6/9/2022 6/9/2025
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 10/14/2024 10/14/2027
Leak Detect - Piping Sump Sensor 10/22/2024 10/22/2025
Spill Contain Device Single Wall Spill Bucket 10/22/2024 10/22/2027
Tank Composite Double Wall Permatank N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 10/22/2024
Tank Composite Double Wall Permatank Precision Test (Tank) Pass 10/22/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors Sensor Functional Pass 10/12/2009



Tank Number 8

Capacity: 7000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/7/2005 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 5/20/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/29/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/22/2024 10/22/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 10/22/2024 10/22/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 10/22/2024 10/22/2025
Overfill Prev Device Overfill Drop Tube Valve 6/30/2022 6/30/2025
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 10/14/2024 10/14/2027
Leak Detect - Piping Sump Sensor 10/22/2024 10/22/2025
Spill Contain Device Single Wall Spill Bucket 10/22/2024 10/22/2027
Tank Composite Double Wall Permatank N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 10/22/2024
Tank Composite Double Wall Permatank Precision Test (Tank) Pass 10/22/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors Sensor Functional Pass 10/12/2009



Tank Number 9

Capacity: 5000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/7/2005 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 5/20/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/29/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/22/2024 10/22/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 10/22/2024 10/22/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 10/22/2024 10/22/2025
Overfill Prev Device Overfill Drop Tube Valve 6/30/2022 6/30/2025
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 10/14/2024 10/14/2027
Leak Detect - Piping Sump Sensor 10/22/2024 10/22/2025
Spill Contain Device Single Wall Spill Bucket 10/22/2024 10/22/2027
Tank Composite Double Wall Permatank N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 10/22/2024
Tank Composite Double Wall Permatank Precision Test (Tank) Pass 10/22/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors Sensor Functional Pass 10/12/2009

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/22/2024 10/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 10/22/2024 10/22/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/22/2024 10/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 10/22/2024 10/22/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/22/2024 10/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 10/22/2024 10/22/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/22/2024 10/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 10/22/2024 10/22/2025

MFD Motorfuel Dispensing Forms

No Forms Found