Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2022949
Status: Active
Facility Name: Ginger's Citgo
Address: 2401 W Diversey Chicago, IL 60647
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z002369
Green Tag Issue Date: 3/12/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Mohammed Badle & Kaiser Sayed
Owner Address: 2401 W Diversey Chicago, IL 60647
Owner Status: Current Owner
Purchase Date: 11/27/2000
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/16/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0030004 Mohammed Badle & Kaiser Sayed Current Owner 11/27/2000
U0023834 BP Amoco Former Owner 4/7/1995
U0027493 Amoco Oil Company Former Owner 1/1/1982
U0000552 BP Products North America, Inc. Former Owner 1/1/1982

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260332 (Pending)    Issue Date: 2/10/2026    Expiration Date: 4/11/2026    View NOV Form

Tanks Violations
1, 2, 3 Line interstitial sensor functional test not accomplished (Required annually). - Dispenser sensor under dispenser 5/6 needs to be tested after replacement.
1, 2, 3 Line leak detection equipment in alarm or failed test, must repair or replace. - Dispenser sensor under dispenser 5/6 failed testing and needs to be replaced
Facility Submit Notification Form for Facility Information Change - https://webapps.sfm.illinois.gov/USTPortal/NotificationForm/Application/GeneralInfo

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
92-3182 Eligible 4/26/1999 5/12/1999 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 44 Abandoned Date:
Install Date: 1/1/1982 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 2/12/2024 2/12/2027
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/4/2026 2/4/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 2/4/2026 2/4/2027
Overfill Prev Device Overfill Drop Tube Valve 2/4/2026 2/4/2029
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 7/14/2025 7/14/2028
Leak Detect - Piping Sump Sensor 2/4/2026 2/4/2027
Spill Contain Device Single Wall Spill Bucket 2/4/2026 2/4/2029
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 44 Abandoned Date:
Install Date: 1/1/1982 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 2/12/2024 2/12/2027
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/4/2026 2/4/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 2/4/2026 2/4/2027
Overfill Prev Device Overfill Drop Tube Valve 2/4/2026 2/4/2029
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 7/14/2025 7/14/2028
Leak Detect - Piping Sump Sensor 2/4/2026 2/4/2027
Spill Contain Device Single Wall Spill Bucket 2/4/2026 2/4/2029
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 44 Abandoned Date:
Install Date: 1/1/1982 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 2/12/2024 2/12/2027
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/4/2026 2/4/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 2/4/2026 2/4/2027
Overfill Prev Device Overfill Drop Tube Valve 2/4/2026 2/4/2029
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 7/14/2025 7/14/2028
Leak Detect - Piping Sump Sensor 2/4/2026 2/4/2027
Spill Contain Device Single Wall Spill Bucket 2/4/2026 2/4/2029
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/14/2025 7/14/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/4/2026 2/4/2027



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/14/2025 7/14/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/4/2026 2/4/2027



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/14/2025 7/14/2028
Leak Detect - Piping Sump Sensor with positive shutdown 1/16/2025 1/16/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/14/2025 7/14/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/4/2026 2/4/2027

MFD Motorfuel Dispensing Forms