Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2022887
Status: Active
Facility Name: Oak Lawn Express Mart, Inc.
Address: 5870 W. 95th Street Oak Lawn, IL 60453
County: Cook
Property Parcel: 24-05-400-063-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000236
Green Tag Issue Date: 10/23/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Oak Law Three Real Estate Inc.
Owner Address: 960 Rand Rd. Suite 208 Des Plaines, IL 60016
Owner Status: Current Owner
Purchase Date: 3/28/2025
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 3/6/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041749 Oak Law Three Real Estate Inc. Current Owner 3/28/2025
U0041243 J & B Oaklawn, Inc. Former Owner 12/17/2019
U0037337 Lehigh Gas Wholesale Services Inc. Former Owner 5/19/2014
U0035189 PAV 2, LLC, Former Owner 1/21/2009
U0023834 BP Amoco Former Owner 4/8/1995
U0027493 Amoco Oil Company Former Owner 1/1/1964
U0000552 BP Products North America, Inc. Former Owner 1/1/1964

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260581 (Pending)    Issue Date: 3/5/2026    Expiration Date: 6/5/2026    View NOV Form

Tanks Violations
6, 8 Double wall piping containment sump not monitored every 30 days or no records available. Perform hydrostatic test on sump.
Facility Financial responsibility must be reported yearly - https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility
6, 8 Line leak detection equipment in alarm or failed test, must repair or replace. - All sensors are under liquid and 5 in alarm and the others are under liquid but not alarming
8 Stick inserted in drop tube overfill device rendering it inoperative - Remove stick. - Also please replace broken fill cap on regular fill pipe
6, 8 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Both STP containments and all dispenser containments are full of liquid. Please remove liquid and repair or replace all containments

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
2024-0539 10/2/2024 Abandonment Log 01141-2024ABN
99-2568 11/16/1999 Removal Log 03047-1999REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
99-2568 Eligible 7/11/2005 7/22/2005 $10,000
20240539 Eligible 9/27/2024 10/4/2024 $5,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 500 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 1/1/1988
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 1/1/1970 Red Tag Issue Date:
Last Used Date: 1/1/1988 Fee Due: $0.00
Product Date: 1/1/1970

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/16/1999
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 1/1/1964 Red Tag Issue Date:
Last Used Date: 11/15/1999 Fee Due: $0.00
Product Date: 1/1/1964

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/16/1999
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: 1/1/1968 Red Tag Issue Date:
Last Used Date: 11/15/1999 Fee Due: $0.00
Product Date: 1/1/1968

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/16/1999
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: 1/1/1968 Red Tag Issue Date:
Last Used Date: 11/15/1999 Fee Due: $0.00
Product Date: 1/1/1968

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/16/1999
OSFM First Notify Date: 2/10/1988 Abandoned Material:
Current Age: 11 Abandoned Date:
Install Date: 1/1/1988 Red Tag Issue Date:
Last Used Date: 11/15/1999 Fee Due: $0.00
Product Date: 1/1/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/7/2000 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 11/19/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/19/1999

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/12/2026 2/12/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 2/12/2026 2/12/2027
Overfill Prev Device Overfill Drop Tube Valve 2/12/2026 2/12/2029
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 10/9/2024 10/9/2027
Leak Detect - Piping Sump Sensor 2/12/2026 2/12/2027
Spill Contain Device Single Wall Spill Bucket 2/12/2026 2/12/2029
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 2/12/2026
Piping Fiberglass Double Wall Precision Test (Piping) Pass 6/20/2022
Tank Fiberglass Double Wall Precision Test (Tank) Pass 6/20/2022
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 3/19/2020



Tank Number 7

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Abandoned in place CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/7/2000 Abandoned Material: Sand
Current Age: 26 Abandoned Date: 10/2/2024
Install Date: 11/19/1999 Red Tag Issue Date:
Last Used Date: 3/30/2018 Fee Due: $0.00
Product Date: 11/19/1999

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/13/2024 3/13/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/13/2024 3/13/2025
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Sump Sensor 3/13/2024 3/13/2025
Spill Contain Device Single Wall Spill Bucket
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 6/20/2022
Tank Fiberglass Double Wall Precision Test (Tank) Pass 6/20/2022



Tank Number 8

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/7/2000 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 11/19/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/19/1999

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/12/2026 2/12/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 2/12/2026 2/12/2027
Overfill Prev Device Overfill Drop Tube Valve 5/10/2024 5/10/2027
Piping Fiberglass Double Wall N/A N/A
Piping Fiberglass Single Wall Piping Ameron 4000 L single wall vent N/A N/A
Piping Single Wall STP/Tanktop Sump 10/9/2024 10/9/2027
Leak Detect - Piping Sump Sensor 2/12/2026 2/12/2027
Spill Contain Device Single Wall Spill Bucket 2/12/2026 2/12/2029
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 6/20/2022
Piping Fiberglass Double Wall Precision Test (Piping) Pass 2/12/2026
Piping Fiberglass Single Wall Piping Ameron 4000 L single wall vent Precision Test (Piping) Pass 2/12/2026
Tank Fiberglass Double Wall Precision Test (Tank) Pass 3/17/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/27/2022 9/27/2025
Leak Detect - Piping Sump Sensor 2/12/2026 2/12/2027



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/27/2022 9/27/2025
Leak Detect - Piping Sump Sensor 4/30/2026 4/30/2027



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/7/2024 10/7/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/30/2026 4/30/2027



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/27/2022 9/27/2025
Leak Detect - Piping Sump Sensor 2/12/2026 2/12/2027



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/27/2022 9/27/2025
Leak Detect - Piping Sump Sensor 2/12/2026 2/12/2027

MFD Motorfuel Dispensing Forms