| 6, 8 |
Double wall piping containment sump not monitored every 30 days or no records available. Perform hydrostatic test on sump. |
| Facility |
Financial responsibility must be reported yearly - https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility |
| 6, 8 |
Line leak detection equipment in alarm or failed test, must repair or replace. - All sensors are under liquid and 5 in alarm and the others are under liquid but not alarming |
| 8 |
Stick inserted in drop tube overfill device rendering it inoperative - Remove stick. - Also please replace broken fill cap on regular fill pipe |
| 6, 8 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Both STP containments and all dispenser containments are full of liquid. Please remove liquid and repair or replace all containments |