Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2022812
Status: Active
Facility Name: Amoco 5464
Address: 1001 S. First Avenue Maywood, IL 60153
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000051
Green Tag Issue Date: 5/22/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Rattansay, Inc.
Owner Address: 1001 S. First Ave. Maywood, IL 60153
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 6/11/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0036540 Rattansay, Inc. Current Owner
U0032360 Angel Associates, LP Former Owner 12/17/2009
U0023834 BP Amoco Former Owner 4/12/1995
U0027493 Amoco Oil Company Former Owner 1/1/1983
U0000552 BP Products North America, Inc. Former Owner 1/1/1983

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020261754 (Pending)    Issue Date: 7/9/2026    Expiration Date: 9/7/2026    View NOV Form

Tanks Violations
2, 3, 4 Dispensers - hoses cracked, split or worn and require replacement
2, 3, 4 Line leak detection equipment in alarm or failed test, must repair or replace. - Tank top sump sensors in alarm
Facility Missing copies of current testing certificates for operator training - Copies must be kept on site
2 Tank monitor does not appear to function properly and requires maintenance. - All lights are out
2 Tank monitor does not appear to function properly and requires maintenance. - Tank top sump sensors are not shutting down the pump despite being positive shut down and in alarm
3 Tank monitor does not appear to function properly and requires maintenance. - All lights are out
3 Tank monitor does not appear to function properly and requires maintenance. - Tank top sump sensors are not shutting down the pump despite being positive shut down and in alarm
4 Tank monitor does not appear to function properly and requires maintenance. - All lights are out
4 Tank monitor does not appear to function properly and requires maintenance. - Tank top sump sensors are not shutting down the pump despite being positive shut down and in alarm
2, 3, 4 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - All UDC's
2, 3, 4 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Provide documentation from a contractor of repair

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
92-1887 Eligible 2/1/1996 3/6/1996 $15,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 1000 Used Oil Removed Federal $0.00 01/01/1992 - REM
2 10000 Gasoline - Regular Currently in use Federal $0.00
3 10000 Gasoline - Regular Currently in use Federal $0.00
4 10000 Gasoline - Premium Currently in use Federal $0.00
5 550 Heating Oil Removed State $0.00 01/01/1992 - REM
6 550 Heating Oil Removed Federal $0.00 01/01/1992 - REM
7 1000 Heating Oil Removed State $0.00 01/01/1992 - REM


Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active


MFD Motorfuel Dispensing Forms