| Facility |
Electrical Does Not Comply - Regular North ATG wiring is open and needs to have an Apoxy Pack. |
| Facility |
Financial responsibility must be reported yearly - (Submit this form after the change of ownership notification form has been approved.) |
| 3 |
Install or replace lockable fill pipe caps. - Premium fill cap is broke. Repair/Replace |
| 1, 2, 3 |
Line leak detection equipment in alarm or failed test, must repair or replace. - L1 and L5 are in alarm. Repair/Replace to fix alarm. |
| 2 |
Miscellaneous - Equipment in disrepair 176.410 ATG cap on the south regular tank is loose. Repair/Replace. |
| 1, 2, 3 |
Piping interstitial must be open in all sumps - Double wall piping is closed in dispensers 1/2, 7/8 and Transition sump. |
| Facility |
Submit Notification Form for Ownership Change - ( Make sure you write down the access Code that is given to you when you start the notification form.) Owner has to match as it appears on the deed. |
| 1, 2, 3 |
Tank monitor does not appear to function properly and requires maintenance. - Indicator light(s) on panel of Veeder-Root ATG is/are not functional. Replace as necessary to provide proper operation. (Green light is not working.) All lights need to be working. |
| 1, 2, 3 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Dispenser 3/4 and Transition sump. Will need to see documentation that containments were fixed. |