Notice of Violatlions (Current)
NOV Number:
E0020260762
(Pending)
Issue Date:
3/20/2026
Expiration Date:
5/19/2026
View NOV Form
| Tanks |
Violations |
| 3, 4 |
Annual line precision and mechanical line leak detector functional test not completed. - Last done March 18, 2025. |
| 1, 2, 3, 4 |
Line interstitial sensor functional test not accomplished (Required annually). - Sensors last tested 3/18/2025 |
| 4 |
Line interstitial sensors have been raised and rendered inoperational. |
| 4 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Fuel Alarm for raised sensor and water in sump. Repair sump and pump out water and reposition sensor to sump floor. |