Notice of Violatlions (Current)
NOV Number:
E0020260629
(Pending)
Issue Date:
3/12/2026
Expiration Date:
5/11/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom. |
NOV Number:
E0020260630
(Pending)
Issue Date:
3/12/2026
Expiration Date:
5/11/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shut off switch needs annual testing performed. OSFM form shall be kept on site. |
| Facility |
Missing copies of Annual Walkthrough Inspection Report. - Annual walkthrough needs to be performed. OSFM form shall be completed and kept on site. |
| 5, 6 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). |
| 5, 6 |
Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Shear valves need annual testing performed. OSFM form shall be completed and kept on site. |
| 5, 6 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Remove liquid |
| 5, 6 |
Tank monitor does not appear to function properly and requires maintenance. - Green and red indicator lights are out and need to be replaced. |
NOV Number:
E0020260692
(Pending)
Issue Date:
3/13/2026
Expiration Date:
5/12/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Financial responsibility must be reported yearly - The form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility |
| Facility |
Submit Notification Form For Ownership Change - The Notification Form is available at: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of an ownership change. |