Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2021180
Status: Active
Facility Name: Circle K #6800
Address: 4 W. Irving Park Road @ York Bensenville, IL 60106
County: Du Page
Property Parcel: 03-14-213-048
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002812
Green Tag Issue Date: 2/6/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: RDK Ventures, LLC
Owner Address: 1120 W. Warner Rd. Tempe, AZ 85284
Owner Status: Current Owner
Purchase Date: 1/7/2010
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 1/26/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/18/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures, LLC Current Owner 1/7/2010
U0027449 Equilon Enterprises, LLC Former Owner 9/14/1988
U0013849 Shell Oil Products Former Owner 12/31/1967
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00846-2025UPG Upgrade Approved / Revised 7/7/2025 7/7/2025 1/7/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020251577 (Pending)    Issue Date: 4/22/2025    Expiration Date: 6/21/2025    View NOV Form

Tanks Violations
5, 6 Tank monitor does not appear to function properly and requires maintenance. - All sensors need to be programmed on the ATG. Dispenser sump sensors are stand alone and need to be on the ATG.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
2022-1104 4/18/2023 Abandonment Log 00094-2023ABN

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
08-1059 Eligible 10/1/2008 11/19/2008 $15,000
20221104 Eligible 4/26/2023 4/26/2023 $5,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 9/12/1988
OSFM First Notify Date: 1/5/1987 Abandoned Material:
Current Age: 17 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 9/12/1988
OSFM First Notify Date: 1/5/1987 Abandoned Material:
Current Age: 17 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 9/12/1988
OSFM First Notify Date: 1/5/1987 Abandoned Material:
Current Age: 17 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 550 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 9/12/1988
OSFM First Notify Date: 1/5/1987 Abandoned Material:
Current Age: 17 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/20/1993 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: 9/14/1988 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/19/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/13/2024 11/13/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 11/13/2024 11/13/2025
Overfill Prev Device Overfill Drop Tube Valve 2/5/2025 2/5/2028
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 1/30/2024 1/30/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 3/9/2021 3/9/2022
Leak Detect - Piping Discriminating Sump Sensor with positive shutdown 1/17/2023 1/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 12/19/2023 12/19/2024
Leak Detect - Piping Sump Sensor with positive shutdown 11/13/2024 11/13/2025
Spill Contain Device Single Wall Spill Bucket 1/30/2024 1/30/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 1/17/2023
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 11/13/2024
Tank Fiberglass Single Wall Precision Test (Tank) Pass 7/12/2024



Tank Number 6

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/20/1993 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: 9/14/1988 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/19/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/13/2024 11/13/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 11/13/2024 11/13/2025
Overfill Prev Device Overfill Drop Tube Valve 2/5/2025 2/5/2028
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 1/30/2024 1/30/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 1/17/2023 1/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 11/13/2024 11/13/2025
Spill Contain Device Single Wall Spill Bucket 1/30/2024 1/30/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 1/17/2023
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 11/13/2024
Tank Fiberglass Single Wall Precision Test (Tank) Pass 1/17/2024



Tank Number 7

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Abandoned in place CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/20/1993 Abandoned Material: Inert material mixed with portland cement
Current Age: 36 Abandoned Date: 4/18/2023
Install Date: 9/14/1988 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/19/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/3/2023 3/3/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 1/17/2023 1/17/2024
Overfill Prev Device Overfill Drop Tube Valve 8/7/2021 8/7/2024
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 3/15/2021 3/15/2024
Leak Detect - Piping Sump Sensor 1/17/2023 1/17/2024
Spill Contain Device Single Wall Spill Bucket 3/15/2021 3/15/2024
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 1/17/2023
Tank Fiberglass Single Wall Precision Test (Tank) Fail 12/15/2022

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/30/2024 1/30/2027
Leak Detect - Piping Sump Sensor with positive shutdown 7/7/2025 7/7/2026



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/30/2024 1/30/2027
Leak Detect - Piping Sump Sensor with positive shutdown 7/7/2025 7/7/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/30/2024 1/30/2027
Leak Detect - Piping Sump Sensor with positive shutdown 7/7/2025 7/7/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/30/2024 1/30/2027
Leak Detect - Piping Sump Sensor with positive shutdown 7/7/2025 7/7/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/30/2024 1/30/2027
Leak Detect - Piping Sump Sensor with positive shutdown 7/7/2025 7/7/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/30/2024 1/30/2027
Leak Detect - Piping Sump Sensor with positive shutdown 7/7/2025 7/7/2026

MFD Motorfuel Dispensing Forms

No Forms Found