Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2021138
Status: Active
Facility Name: Circle K #6727
Address: 801 West Main West Dundee, IL 60118
County: Kane
Property Parcel: 03-22-376-029
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001429
Green Tag Issue Date: 5/1/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: RDK Ventures LLC
Owner Address: 1120 W. Warner Rd. Tempe, AZ 85284
Owner Status: Current Owner
Purchase Date: 1/7/2010
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/27/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures LLC Current Owner 1/7/2010
U0013849 Shell Oil Products Former Owner 12/31/1967
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner
U0027449 Equilon Enterprises, LLC Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260902 (Pending)    Issue Date: 4/2/2026    Expiration Date: 6/1/2026    View NOV Form

Tanks Violations
2 Line leak detection equipment in alarm or failed test, must repair or replace. - Leak detector(s) failed annual testing. Repair/replace as necessary. Repaired/replaced leak detector(s) shall be retested to show passing results. Failed 3/17/2026 by Tanknology, East RUL LD (Feeds 1-5) would not catch a simulated leak.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/26/1986 Abandoned Material:
Current Age: 45 Abandoned Date:
Install Date: 12/20/1980 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/21/1980

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 1/8/2026 1/8/2029
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/17/2026 3/17/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/17/2026 3/17/2027
Overfill Prev Device Overfill Drop Tube Valve 5/17/2024 5/17/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Stand Alone Sump Sensor Non-Discriminating 6/2/2022 6/2/2023
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Double Wall Spill Bucket 5/17/2024 5/17/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 3/17/2026
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 3/8/2010



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Mid-grade CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/26/1986 Abandoned Material:
Current Age: 45 Abandoned Date:
Install Date: 12/20/1980 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/21/1980

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 1/8/2026 1/8/2029
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/26/2025 3/17/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/17/2026 3/17/2027
Overfill Prev Device Overfill Drop Tube Valve 5/17/2024 5/17/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Stand Alone Sump Sensor Non-Discriminating 6/2/2022 6/2/2023
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Double Wall Spill Bucket 3/17/2026 3/17/2029
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 3/26/2025
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 3/8/2010



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/26/1986 Abandoned Material:
Current Age: 45 Abandoned Date:
Install Date: 12/20/1980 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/21/1980

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 1/8/2026 1/8/2029
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/23/2026 4/23/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/17/2026 3/17/2027
Overfill Prev Device Overfill Drop Tube Valve 4/25/2024 4/25/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Stand Alone Sump Sensor Non-Discriminating 6/2/2022 6/2/2023
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Double Wall Spill Bucket 3/17/2026 3/17/2029
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 3/17/2026
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 3/8/2010

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A



Name\ID 5

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A



Name\ID 6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A

MFD Motorfuel Dispensing Forms