Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0040487 |
Peoria Packing Roosevelt Property, LLC |
Current Owner |
1/28/2022 |
| U0011727 |
Peoples Gas Light & Coke Company |
Former Owner |
1/1/2000 |
Notice of Violations (Current)
NOV Number:
E0020221817
(Pending)
Issue Date:
6/6/2022
Expiration Date:
8/5/2022
View NOV Form
| Tanks |
Violations |
| 1, 2, 3 |
Perform a site assessment - Tanks 1, 2 & 3 were removed on 10/19/20. Per Il. Adm. Code 176.330, a site assessment must be conducted at time of removal by a supervising Licensed Professional Engineer (PE) or Professional Geologist (PG). Within 45 days after receipt of lab results from the full site assessment, a “Site Assessment Results” form along with the analytical data must be submitted electronically to the OSFM by the supervising PE or PG. The form can be obtained at: https://webapps.sfm.illinois.gov/USTPortal/Forms/SiteAssessmentResults. |
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 12-1039 |
10/3/2012 |
Removal Log |
123177 |
| 20-0882 |
10/19/2020 |
Removal Log |
01365-2020REM |
| 2023-0569 |
7/17/2023 |
Removal Log |
00716-2023REM |
| N/A |
3/10/2022 |
Removal Log |
00183-2022REM |
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
15000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
10/19/2020 |
|
OSFM
First Notify Date: |
11/25/1987 |
|
Abandoned Material: |
|
| Current Age: |
24 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
8/10/2020 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Cathodic Protection |
8/23/2018 |
8/23/2021 |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
8/12/2019 |
8/12/2020 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
8/12/2019 |
8/12/2020 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
12/30/2019 |
12/30/2022 |
|
Piping
|
Steel Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
12/30/2019 |
12/30/2022 |
|
Tank
|
Fiberglass Single Wall Owens Corning |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Steel Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
8/12/2019
|
Tank Number 2
| Capacity: |
15000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
10/19/2020 |
|
OSFM
First Notify Date: |
11/25/1987 |
|
Abandoned Material: |
|
| Current Age: |
24 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
8/10/2020 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Cathodic Protection |
8/23/2018 |
8/23/2021 |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
8/12/2019 |
8/12/2020 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
8/12/2019 |
8/12/2020 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
12/30/2019 |
12/30/2022 |
|
Piping
|
Steel Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
12/30/2019 |
12/30/2022 |
|
Tank
|
Fiberglass Single Wall Owens Corning |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Steel Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
8/12/2019
|
Tank Number 3
| Capacity: |
6000 |
|
Petroleum Use: |
None |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
10/19/2020 |
|
OSFM
First Notify Date: |
11/25/1987 |
|
Abandoned Material: |
|
| Current Age: |
24 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
8/10/2020 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Cathodic Protection |
8/23/2018 |
8/23/2021 |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
8/12/2019 |
8/12/2020 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
8/12/2019 |
8/12/2020 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
9/27/2018 |
9/27/2021 |
|
Piping
|
Steel Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
9/27/2018 |
9/27/2021 |
|
Tank
|
Fiberglass Single Wall Owens Corning |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Steel Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
8/12/2019
|
Tank Number 4
| Capacity: |
550 |
|
Petroleum Use: |
|
| Product: |
Used Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
6/28/1995 |
|
OSFM
First Notify Date: |
11/25/1987 |
|
Abandoned Material: |
|
| Current Age: |
10 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
6/26/1995 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 5
| Capacity: |
15000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
10/3/2012 |
|
OSFM
First Notify Date: |
11/25/1987 |
|
Abandoned Material: |
Inert material mixed with portland cement |
| Current Age: |
45 |
|
Abandoned Date: |
8/1/1974 |
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
8/1/1974 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 6
| Capacity: |
1000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Abandoned in place |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
11/25/1987 |
|
Abandoned Material: |
Inert material mixed with portland cement |
| Current Age: |
42 |
|
Abandoned Date: |
8/1/1974 |
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
8/1/1974 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 7
| Capacity: |
250 |
|
Petroleum Use: |
None |
| Product: |
Waste Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
3/10/2022 |
|
OSFM
First Notify Date: |
3/17/2022 |
|
Abandoned Material: |
|
| Current Age: |
|
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
12/31/1973 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 8
| Capacity: |
1000 |
|
Petroleum Use: |
|
| Product: |
Heating Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
7/17/2023 |
|
OSFM
First Notify Date: |
|
|
Abandoned Material: |
|
| Current Age: |
|
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
12/31/1973 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 9
| Capacity: |
550 |
|
Petroleum Use: |
|
| Product: |
Heating Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
7/17/2023 |
|
OSFM
First Notify Date: |
|
|
Abandoned Material: |
|
| Current Age: |
|
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/1973 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 5/6
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 7/8
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found