Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2020659
Status: Active
Facility Name: Veelani LLC
Address: 213 S. Main Street Elburn, IL 60119
County: Kane
Property Parcel: 11-05-155-001
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001442
Green Tag Issue Date: 5/10/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Veelani LLC
Owner Address: 213 S. Main St. Elburn, IL 60119
Owner Status: Current Owner
Purchase Date: 1/30/2026
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 3/12/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041755 Veelani LLC Current Owner 1/30/2026
U0035867 Elburn Real Estate, LLC Former Owner 6/1/2009
U0032209 Combined Real Estate, LLC Former Owner 7/29/2004
U0007721 J & L Oil Co., Inc. Former Owner 6/1/1968

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00397-2026UPG Upgrade Cancelled by Contractor 4/9/2026 4/9/2026 10/9/2026 Documents
00533-2026UPG Upgrade Approved / Issued 5/12/2026 5/12/2026 11/13/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020260634 (Pending)    Issue Date: 3/12/2026    Expiration Date: 5/11/2026    View NOV Form

Tanks Violations
4 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Section 175.410 Submersible, Under-dispenser, Transition and Other Containment Sumps a) All containment sumps must consist of a factory manufactured containment that is liquid-tight on its sides, bottom and at any penetrations and is compatible with the substance conveyed by the piping. Such containment shall also have a factory manufactured protective cover and supporting components that are properly maintained. If the protective cover or its supporting components are cracked, deteriorated, or missing, the cover and supporting components that are defective shall be replaced. SPECIFICALLY THE DIESEL STP LIDS WITH SAFETY CONE OVER IT.
1 Open electrical conduit or junction boxes. - JUNCTION BOX AT ATG MANWAY HAS BROKEN CAP WITH EXPOSED WIRING. REPLACE JUNCTION BOX.
1, 2, 3, 4 Required monthly tank leak test records not available. - NEW OWNER EFFECTIVE 1/23/2026. FEB MONTHLY MISSING PASS ON PREM TANK. Maintain one PASSing report per TANK, per month, from ATG. Must maintain 24 months’ .
1, 2, 3, 4 Tank monitor does not appear to function properly and requires maintenance. - Indicator lights on panel of Veeder-Root ATG are not functional. Replace all 3 lights as necessary to provide proper operation.

NOV Number: E0020260635 (Pending)    Issue Date: 3/12/2026    Expiration Date: 5/11/2026    View NOV Form

Tanks Violations
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - Self-service instructional signs at dispensers are missing or do not meet minimum requirements. Install appropriate signage for dispenser 1 & 4.
Facility Fire Extinguishers - Past due for annual testing - Fire extinguishers require annual testing. Have annual testing performed and tag all fire extinguishers accordingly.
Facility Miscellaneous - Provide appropriate collision protection for LP tank cage

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
96-2013 Eligible 7/22/2004 8/10/2004 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/28/1986 Abandoned Material:
Current Age: 41 Abandoned Date:
Install Date: 4/12/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/12/1985

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/16/2023 10/16/2026
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 1/24/2024 1/24/2027
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/26/2025 8/26/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/26/2025 8/26/2026
Overfill Prev Device Overfill Alarm 6/5/2024 6/5/2027
Overfill Prev Device Overfill Drop Tube Valve 6/5/2024 6/5/2027
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/5/2024 6/5/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive Precision Test (Piping) Pass 10/16/2024
Tank STIP3 Single Wall Precision Test (Tank) Pass 5/10/2024



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/28/1986 Abandoned Material:
Current Age: 41 Abandoned Date:
Install Date: 4/12/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/12/1985

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/16/2023 10/16/2026
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 1/24/2024 1/24/2027
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/26/2025 8/26/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/26/2025 8/26/2026
Overfill Prev Device Overfill Alarm 6/5/2024 6/5/2027
Overfill Prev Device Overfill Drop Tube Valve 6/5/2024 6/5/2027
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/5/2024 6/5/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive Precision Test (Piping) Pass 10/16/2024
Tank STIP3 Single Wall Precision Test (Tank) Pass 5/10/2024



Tank Number 3

Capacity: 6000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/28/1986 Abandoned Material:
Current Age: 41 Abandoned Date:
Install Date: 4/12/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/12/1985

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/16/2023 10/16/2026
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 1/24/2024 1/24/2027
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/26/2025 8/26/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/26/2025 8/26/2026
Overfill Prev Device Overfill Alarm 6/5/2024 6/5/2027
Overfill Prev Device Overfill Drop Tube Valve 6/5/2024 6/5/2027
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/5/2024 6/5/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive Precision Test (Piping) Pass 10/16/2024
Tank STIP3 Single Wall Precision Test (Tank) Pass 5/10/2024



Tank Number 4

Capacity: 4000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/28/1986 Abandoned Material:
Current Age: 41 Abandoned Date:
Install Date: 4/12/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/12/1985

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/16/2023 10/16/2026
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 1/24/2024 1/24/2027
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/26/2025 8/26/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 8/26/2025 8/26/2026
Overfill Prev Device Overfill Alarm 6/5/2024 6/5/2027
Overfill Prev Device Overfill Drop Tube Valve 6/5/2024 6/5/2027
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/5/2024 6/5/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive Precision Test (Piping) Pass 10/16/2024
Tank STIP3 Single Wall Precision Test (Tank) Pass 5/10/2024



Tank Number 5

Capacity: 2000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Does Not Exist CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/28/1986 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 9/1/1998
OSFM First Notify Date: 4/28/1986 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 1/1/1982 Red Tag Issue Date:
Last Used Date: 1/1/1902 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 7

Capacity: 1000 Petroleum Use:
Product: Kerosene CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 9/1/1996
OSFM First Notify Date: 4/28/1986 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 1/1/1902 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 8

Capacity: 1000 Petroleum Use: Consumptive Use on Premises for Heating
Product: Heating Oil CERCLA Substance:
Status: Does Not Exist CAS Code:
Regulated Status: State Removed Date:
OSFM First Notify Date: 6/12/1992 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 6/1/1976 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/26/2025 8/26/2028
Leak Detect - Piping Sump Sensor 8/26/2025 8/26/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/26/2025 8/26/2028
Leak Detect - Piping Sump Sensor 8/26/2025 8/26/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/26/2025 8/26/2028
Leak Detect - Piping Sump Sensor 8/26/2025 8/26/2026

MFD Motorfuel Dispensing Forms