Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2020619
Status: Active
Facility Name: Lucas Carrillo d/b/a Sinhas Gas Mart, Inc.
Address: 1116 East New York Aurora, IL 60505
County: Kane
Property Parcel: 15-23-454-018
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000207
Green Tag Issue Date: 5/30/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Upendra Sinha, MD
Owner Address: 2931 Willow Ridge Drive Naperville, IL 60564
Owner Status: Current Owner
Purchase Date: 3/21/2002
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 6/25/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040010 Sinha, MD, Upendra Current Owner 3/21/2002
U0034799 Sumitra International, Inc. Former Owner 12/15/2002
U0030819 Sinhas Gas Mart, Inc. Former Owner 4/17/2002
U0006490 Harper Oil Company Former Owner 5/1/1971

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260862 (Pending)    Issue Date: 4/1/2026    Expiration Date: 5/31/2026    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shut off switch needs annual testing performed. OSFM form shall be kept on site.
4, 5, 6 Document that emergency shut-off (shear valves) are in proper working order - Shear valves need annual testing performed. OSFM form shall be completed and kept on site.
4 Miscellaneous - ATG shows Q1 Annual Line Fail
5 Miscellaneous - ATG shows Premium tank test invalid.
5 Miscellaneous - Fill Cap Is Broken
6 Miscellaneous - ATG shows Q1 Annual Line Fail
6 Miscellaneous - Vapor cover is broken
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual walkthrough needs to be performed. OSFM form shall be completed and kept on site.
4, 5, 6 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
93-1491 10/21/1993 Removal Log

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
93-1491 Eligible 9/14/1993 11/29/1993 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline Removed Federal $0.00 10/21/1993 - REM
2 8000 Gasoline Removed Federal $0.00 10/21/1993 - REM
3 8000 Gasoline Removed Federal $0.00 10/21/1993 - REM
4 10000 Gasoline - Regular Currently in use Federal $0.00
5 10000 Gasoline - Premium Currently in use Federal $0.00
6 10000 Gasoline - Regular Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active

MFD Motorfuel Dispensing Forms