| 1, 2 |
Dispensers - the following hoses or breakaways are missing or actively leaking and require immediate replacement (bagged at inspection) - Replace Brakeaway. Can not be held together with ducktape. |
| 2 |
Install or replace lockable fill pipe caps. - Premium snap cap is missing it's gasket. Repair/Replace |
| 1, 2, 3 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
| 1, 3 |
Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. - Will need documentation showing that the containments have been fixed and testing results. (Regular and E-85) |