Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2020405
Status: Active
Facility Name: Green Park Corporation
Address: 2755 W. 87th St. Evergreen Park, IL 60805
County: Cook
Property Parcel: 24-01-200-065-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001358
Green Tag Issue Date: 12/18/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Green Park Corporation
Owner Address: 2755 W. 87th Street Evergreen Park, IL 60805
Owner Status: Current Owner
Purchase Date: 12/4/2015
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 10/15/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038162 Green Park Corporation Current Owner 12/4/2015
U0033779 SVT Masters Corp. Former Owner 4/30/2004
U0008193 Kean Oil Co Former Owner 7/11/1995
U0017400 Phillips 66 Former Owner 5/5/1995
U0024135 Kl Oil Co Former Owner 12/31/1967
U0029824 Siddiqui, Khalid Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260881 (Pending)    Issue Date: 4/2/2026    Expiration Date: 6/1/2026    View NOV Form

Tanks Violations
4 Failed to Empty the Tank to 1" or Less - Diesel tank needs to be emptied.
1, 2, 3, 4 Line interstitial sensors have been raised and rendered inoperational. - All Dispensers
1 Open electrical conduit or junction boxes. - Closests Regular to the store atg juction box is missing it's cap. Repair/Replace
1, 3, 4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
4 Submit Notification Form For Tank Status Change - The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of a tank status change. (Tank out of Service)
1, 3, 4 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Regular, Premium, and Diesel STPs. Also dispensers 3/4,7/8, and 5/6.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
20160804 Eligible 12/16/2016 12/16/2016 $5,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 53 Abandoned Date:
Install Date: 1/1/1973 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1973

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/3/2026 2/3/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 2/3/2026 2/3/2027
Overfill Prev Device Overfill Drop Tube Valve 10/1/2024 10/1/2027
Piping Flexible Double Wall Total Containment Omniflex I N/A N/A
Piping Single Wall STP/Tanktop Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 7/11/2022 7/11/2023
Leak Detect - Piping Sump Sensor with positive shutdown 2/3/2026 2/3/2027
Spill Contain Device Single Wall Spill Bucket 10/1/2024 10/1/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Omniflex I Precision Test (Piping) Pass 2/3/2026
Piping Galvanized Steel Single Wall Piping Precision Test (Piping) Pass 7/11/2022



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 53 Abandoned Date:
Install Date: 1/1/1973 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1973

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/3/2026 2/3/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 2/3/2026 2/3/2027
Overfill Prev Device Overfill Drop Tube Valve 10/1/2024 10/1/2027
Piping Flexible Double Wall Total Containment Omniflex I N/A N/A
Piping Single Wall STP/Tanktop Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 2/3/2026 2/3/2027
Spill Contain Device Single Wall Spill Bucket 10/1/2024 10/1/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Omniflex I Precision Test (Piping) Pass 2/3/2026
Piping Galvanized Steel Single Wall Piping Precision Test (Piping) Pass 7/11/2022



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 53 Abandoned Date:
Install Date: 1/1/1973 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1973

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/3/2026 2/3/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 2/3/2026 2/3/2027
Overfill Prev Device Overfill Drop Tube Valve 10/1/2024 10/1/2027
Piping Flexible Double Wall Total Containment Omniflex I N/A N/A
Piping Single Wall STP/Tanktop Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 2/3/2026 2/3/2027
Spill Contain Device Double Wall Spill Bucket 10/1/2024 10/1/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Omniflex I Precision Test (Piping) Pass 2/3/2026
Piping Galvanized Steel Single Wall Piping Precision Test (Piping) Pass 7/11/2022



Tank Number 4

Capacity: 2000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/13/1996 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: 11/26/1996 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/3/2026 2/3/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 2/3/2026 2/3/2027
Overfill Prev Device Overfill Drop Tube Valve 10/1/2024 10/1/2027
Piping Flexible Double Wall Total Containment Omniflex I N/A N/A
Piping Single Wall STP/Tanktop Sump 10/1/2024 10/1/2027
Leak Detect - Piping Discriminating Sump Sensor 3/10/2021 3/10/2022
Leak Detect - Piping Sump Sensor 2/3/2026 2/3/2027
Spill Contain Device Single Wall Spill Bucket 10/1/2024 10/1/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Omniflex I Precision Test (Piping) Pass 2/3/2026



Tank Number 5

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Does Not Exist CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 12000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Does Not Exist CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection
Leak Detect - Piping Sump Sensor
Leak Detect - Tank Automatic Tank Gauging Gilbarco EMC
Overfill Prev Device Overfill Drop Tube Valve
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 7

Capacity: 2500 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Does Not Exist CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection
Leak Detect - Piping Sump Sensor
Leak Detect - Tank Automatic Tank Gauging Gilbarco EMC
Overfill Prev Device Overfill Drop Tube Valve
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 2/3/2026 2/3/2027



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 2/3/2026 2/3/2027



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor with positive shutdown 2/3/2026 2/3/2027



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor 2/3/2026 2/3/2027



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/1/2024 10/1/2027
Leak Detect - Piping Sump Sensor with positive shutdown 2/3/2026 2/3/2027

MFD Motorfuel Dispensing Forms

No Forms Found