Notice of Violatlions (Current)
NOV Number:
E0020260269
(Pending)
Issue Date:
2/3/2026
Expiration Date:
4/4/2026
View NOV Form
| Tanks |
Violations |
| 3 |
Line interstitial sensors have been raised and rendered inoperational. - Dispenser 1/2 has raised sensr. Sensor must be lowered to the bottom of the sump or manufactures specifications. |
| 1 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Remove liquid |
| 1, 2, 3, 4 |
Tank monitor does not appear to function properly and requires maintenance. - ATG in alarm; repair/replace as necessaryto secure alarm |
| 1, 2, 3, 4 |
Tank sacrificial anode system not tested (Required every 3 years). |
NOV Number:
E0020260273
(Pending)
Issue Date:
2/3/2026
Expiration Date:
4/4/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Code complying instruction/warning signs are not properly mounted at each dispenser island - Minimum signage requires letters shall not be less than 7/8” in height. The top of the sign shall be mounted no higher than 10’ above grade. The wording shall include a minimum of 1) “Warning” 2) “Stop Engine” 3) “No Smoking” 4) “Persons fueling vehicles shall remain with their vehicle, at the nozzle, while fueling is in progress” 5) “It is unlawful and dangerous for anyone to dispense gasoline into unapproved containers” |