Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2020221
Status: Active
Facility Name: BP Carpentersville
Address: 170 Lake Marian Road Carpentersville, IL 60110
County: Kane
Property Parcel: 03-14-135-007
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001441
Green Tag Issue Date: 5/10/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Carpentersville Building, LLC
Owner Address: 170 Lake Marian Road Carpentersville, IL 60110
Owner Status: Current Owner
Purchase Date: 2/12/2024
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 2/28/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041196 Carpentersville Building, LLC Current Owner 2/12/2024
U0038564 BETU Corporation, Inc. Former Owner 9/7/2016
U0028177 Sidlo Petroleum Former Owner 12/1/2000
U0001237 Kaczmarek, Tom Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260474 (Pending)    Issue Date: 2/25/2026    Expiration Date: 4/26/2026    View NOV Form

Tanks Violations
Facility Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - Section 175.210g; All dispensing units shall be readily visible from the control station without assistive devices. If view is permanently obstructed, or the dispenser is located so that activity is not readily visible, closed-circuit cameras that provide a view of each side of the dispensing unit and project an image on a screen at least 6 inches in diagonal located at the control station may be used. You may also elect to install an emergency stop switch at least 20 feet but no more than 50 feet from any dispenser with a permanently obstructed view.
Facility Miscellaneous - LP COLLISION PROTECTION.

NOV Number: E0020260475 (Pending)    Issue Date: 2/25/2026    Expiration Date: 4/26/2026    View NOV Form

Tanks Violations
7 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Section 175.410 Submersible, Under-dispenser, Transition and Other Containment Sumps a) All containment sumps must consist of a factory manufactured containment that is liquid-tight on its sides, bottom and at any penetrations and is compatible with the substance conveyed by the piping. Such containment shall also have a factory manufactured protective cover and supporting components that are properly maintained. If the protective cover or its supporting components are cracked, deteriorated, or missing, the cover and supporting components that are defective shall be replaced. PREMIUM STP LID NEEDS HANDLE REPLACED.
Facility Electrical Does Not Comply - PREM AND REG JUNCTION BOX NEEDS REPLACEMENT/ OPEN ELECTRICAL ALSO WHAT APPEARS TO BE VAPOR RECOVERY RISER OR AN EXTRA RISER, HAS A SAFETY CONE STICKING OUT OF THE RISER AS A CAP. REPLACE JUNCTION BOXES, CAP OFF ALL EXPOSED WIRING, REPLACE CONE WITH MANUFACTURER CAP.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and 2 years of documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom.
6, 7 Precision tank test required. - Precision tank test is required on tanks.
6, 7 Required monthly tank leak test records not available. - Maintain one PASSing report per TANK, per month, from ATG. Must maintain 24 months’ worth.
6, 7 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
7 Tank monitor does not appear to function properly and requires maintenance. - TANK FAIL 0.2 TEST. PRECISION TEST TANK AND UPLOAD PASSING RESULTS.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
00-2042 10/25/2000 Abandonment Log 03355-1999ABN
99-2532 5/11/2017 Abandonment Log 00400-2017ABN

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
20002042 Eligible 12/6/2016 12/7/2016 $10,000 Letter
19992532 Eligible 12/6/2016 12/7/2016 $10,000 Letter
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Diesel Fuel Abandoned in place Federal $0.00 05/11/2017 - ABN
2 4000 Gasoline Abandoned in place Federal $0.00 10/25/2000 - ABN
3 4000 Gasoline Abandoned in place Federal $0.00 10/25/2000 - ABN
4 4000 Gasoline Abandoned in place Federal $0.00 10/25/2000 - ABN
5 1000 Heating Oil Removed State $0.00 06/01/1990 - REM
6 10000 Gasoline - Regular Currently in use Federal $0.00
7 4000 Gasoline - Premium Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
2020221 BP Carpentersville Carpentersville 09/02/2025 Letter Form