Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2020220
Status: Active
Facility Name: Hebron Country Store
Address: 10010 Main Street Hebron, IL 60034
County: McHenry
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001416
Green Tag Issue Date: 4/12/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Tom Kaczmarek
Owner Address: PO Box 406 Hebron, IL 60034
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 8/7/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0001237 Kaczmarek, Tom Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260509 (Pending)    Issue Date: 2/27/2026    Expiration Date: 4/28/2026    View NOV Form

Tanks Violations
Facility Fire Extinguishers - 2 4A:60BC extinguishers not provided - Provide min of 2 fire extinguishers (4A:60 BC rated), installed to provide access to both employees and customers. THE 2ND FIRE EXTINGUISHER IS IN A BACK ROOM, NOT LABELED AND NOT ACCESSIBLE TO CUSTOMERS.

NOV Number: E0020260512 (Pending)    Issue Date: 2/27/2026    Expiration Date: 4/28/2026    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain 2 years on site with other annual testing documentation.
Facility Facility Operation and Maintenance Plan not completed or available. - Adopt and implement a written operations and maintenance plan, signed by both the owner and either a Class A or Class B Operator designated for the UST facility An Operations & Maintenance template is available at www.sfm.illinois.gov to download and complete O & M template and maintain completed form on site.
Facility Miscellaneous - OUTSIDE AND CONTROL STATION EMERGENCY STOP SWITCHES NEED TO HAVE IDENTIFYING PLACARD. CONTROL STATION EMERGENCY STOP SWITH NEEDS TO BE UNBLOCKED AND EASILY ACCESSIBLE.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and 2 years of documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures plan shall be maintained on site for viewing and reference as necessary (See Operator Training Rules 176.645). The emergency plan template is available on the OSFM website.
Facility Missing list of designated Class A/B & C Operators
2, 3, 5 Monthly line interstitial sensor records not available.
2, 3, 5 Precision tank test required. - Precision tank test is required on tank(s) if you cannot provide 24 months’ worth of tank “NORMAL” from ATG.
2, 3, 5 Required monthly tank leak test records not available. - Maintain one PASSing report per TANK, per month, from ATG. Must maintain 24 months’ worth.
2, 3, 5 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Must maintain 2 years of inspection reports.
2, 3, 5 Tank monitor does not appear to function properly and requires maintenance. - ATG in alarm; repair/replace as necessary to secure alarm.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
99-1107 5/5/1999 Removal Log 01672-1999REM

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 3000 Gasoline Removed Federal $0.00 05/05/1999 - REM
2 3000 Gasoline - Premium Currently in use Federal $0.00
3 3000 Gasoline - Regular Currently in use Federal $0.00
4 1000 Kerosene Removed Federal $0.00 05/05/1999 - REM
5 4000 Gasoline - Regular Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active

MFD Motorfuel Dispensing Forms

No Forms Found