Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2018776
Status: Inactive
Facility Name: Central Fire Station
Address: 75 N Broadway St. Aurora, IL 60507
County: Kane
Property Parcel: 15-22-328-033
Facility Type: City / Town
Owner Type: Other Local
Green Tag Decal: Z004144
Green Tag Issue Date: 8/15/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Fleet

Owner Details

Owner Name: City of Aurora
Owner Address: 44 E. Downer Place P.O. Box 2067 Aurora, IL 60507
Owner Status: Current Owner
Purchase Date: 4/1/1980
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 10/1/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0000960 City of Aurora Current Owner 4/1/1980

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
01290-2026UPG Upgrade Approved / Issued 10/19/2026 10/19/2026 4/20/2027 Documents

Notice of Violations (Current)

NOV Number: E0020262356 (Pending)    Issue Date: 10/15/2026    Expiration Date: 12/14/2026    View NOV Form

Tanks Violations
4, 5 Failed to Empty the Tank to 1" or Less - Per 175.810(a) (1), when placing tanks out of service, the tanks and lines must be emptied immediately. The UST is considered empty when all materials have been removed to one inch or less. As of 10/15/2026, tank 4 has 3,215 gallons or approximately 64 inches of product and tank 5 has 86 gallons or approximately 6.23 inches of product in the tank, as confirmed by the automatic tank gauge.
4, 5 Submit Notification Form For OOS Tank Status Change - Per 175.810(a) (3), tanks taken out of service are required to notify the OSFM within 30 days of the date of last use, on an electronic Notification for Underground Storage Tank form, declaring a tank status change. These tanks have been out of service since 8/5/2026 for repair to the interstitial monitoring, thus far no repairs have been made. Here is the link to the electronic Notification for Underground Storage Tank form, so you can file that change: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
96-1239 Eligible 8/13/1996 9/25/1996 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 2000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/11/1996
OSFM First Notify Date: 4/6/1986 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 4/1/1980 Red Tag Issue Date:
Last Used Date: 7/10/1996 Fee Due: $0.00
Product Date: 4/1/1980

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed




Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/11/1996
OSFM First Notify Date: 4/6/1986 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 4/1/1980 Red Tag Issue Date:
Last Used Date: 7/10/1996 Fee Due: $0.00
Product Date: 4/1/1980

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed




Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/11/1996
OSFM First Notify Date: 4/6/1986 Abandoned Material:
Current Age: 16 Abandoned Date:
Install Date: 4/1/1980 Red Tag Issue Date:
Last Used Date: 7/10/1996 Fee Due: $0.00
Product Date: 4/1/1980

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed




Tank Number 4

Capacity: 4000 Petroleum Use: Dispensing
Product: Diesel Fuel CERCLA Substance:
Status: Out of service CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/13/1996 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 7/25/1996 Red Tag Issue Date: 10/15/2026
Last Used Date: 8/5/2026 Fee Due: $0.00
Product Date: 8/2/1996

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 9/8/2025 9/8/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS - 4c 9/8/2025 9/8/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 9/8/2025 9/8/2026
Overfill Prev Device Overfill Drop Tube Valve 9/26/2023 9/26/2026
Piping Fiberglass Double Wall Ameron Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 9/26/2023 9/26/2026
Leak Detect - Piping Sump Sensor 9/26/2023 9/26/2026
Spill Contain Device Single Wall Spill Bucket 9/26/2023 9/26/2026
Tank Fiberglass Double Wall XERXES Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test (Piping) Pass 9/8/2025



Tank Number 5

Capacity: 3000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Out of service CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/13/1996 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 7/25/1996 Red Tag Issue Date: 8/5/2026
Last Used Date: 8/5/2026 Fee Due: $0.00
Product Date: 8/2/1996

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 9/8/2025 9/8/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS - 4c 9/8/2025 9/8/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 9/8/2025 9/8/2026
Overfill Prev Device Overfill Drop Tube Valve 9/26/2023 9/26/2026
Piping Fiberglass Double Wall Ameron Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 9/26/2023 9/26/2026
Leak Detect - Piping Sump Sensor 9/26/2023 9/26/2026
Spill Contain Device Single Wall Spill Bucket 9/26/2023 9/26/2026
Tank Fiberglass Double Wall XERXES Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test (Piping) Pass 9/8/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Fail 7/29/2026

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


MFD Motorfuel Dispensing Forms

No Forms Found