| 9, 10 |
Annual electronic line leak detector test not completed. |
| Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs and dispensers. Form can be found at https://sfm.illinois.gov to download and complete |
| 9, 10 |
Annual leak detection certification not completed (Required annually). - ATG Cert. |
| Facility |
Financial responsibility must be reported yearly - Financial Responsibility form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility |
| 9 |
Install or replace lockable fill pipe caps. - Need a pad lock on the snap cap or change to a closed cap. |
| 9, 10 |
Line interstitial sensor functional test not accomplished (Required annually). |
| Facility |
Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough shall be performed by a licensed contractor shall be conducted and documentation maintained on site. |
| 9, 10 |
Piping interstitial must be open in all sumps - STP INT's are closed. |
| 9, 10 |
Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Go to https://sfm.illinois.gov to print out the Shear Valve inspection form. |
| 9, 10 |
Tank monitor does not appear to function properly and requires maintenance. - Indicator light(s) on panel of Veeder-Root ATG is/are not functional. Replace as necessary to provide proper operation. (Green Light is Out) |