Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2018070
Status: Active
Facility Name: County of McHenry - Sheriff's Garage
Address: 2200 N. Seminary Ave., Annex A Woodstock, IL 60098
County: McHenry
Property Parcel:
Facility Type: County
Owner Type: County
Green Tag Decal: Z003995
Green Tag Issue Date: 4/11/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Fleet

Owner Details

Owner Name: County of McHenry
Owner Address: 2200 N. Seminary Ave. Woodstock, IL 60098
Owner Status: Current Owner
Purchase Date: 9/1/1989
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 8/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0009984 County of McHenry Current Owner 9/1/1989

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260971 (Pending)    Issue Date: 4/10/2026    Expiration Date: 6/9/2026    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain 2 years on site with other annual testing documentation.
4, 5 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
4, 5 Annual line precision and mechanical line leak detector functional test not completed. - Annual third-party precision line and leak detector test is required.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site.
4, 5 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Triennial inspection of overfill device (drop tube valve and overfill alarm) has not been completed. Testing shall be completed with passing results and uploaded to OSFM website.
4, 5 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Must maintain 2 years of inspection reports.
4, 5 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
902484 8/28/1990 Removal Log

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 6000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/28/1990
OSFM First Notify Date: 4/1/1986 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/1/1989
OSFM First Notify Date: 4/1/1986 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 11/1/1989 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 6000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Moved CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/3/1992 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 10/1/1991 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/1/1991

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Piping Sump Sensor 3/21/2014 3/21/2015
Leak Detect - Tank Automatic Tank Gauging Incon TS 750
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/21/2014 3/21/2015
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Double Wall N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/1/1994 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: 11/1/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/21/2026 4/21/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300i with CSLD 4/21/2026 4/21/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/21/2026 4/21/2027
Overfill Prev Device Overfill Alarm 4/21/2026 4/21/2029
Overfill Prev Device Overfill Drop Tube Valve 4/21/2026 4/21/2029
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 4/21/2026 4/21/2029
Leak Detect - Piping Sump Sensor 4/21/2026 4/21/2027
Spill Contain Device Single Wall Spill Bucket 4/21/2026 4/21/2029
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 4/21/2026



Tank Number 5

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/1/1994 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: 11/1/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/21/2026 4/21/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300i with CSLD 4/21/2026 4/21/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/1/2026 5/1/2027
Overfill Prev Device Overfill Alarm 4/21/2026 4/21/2029
Overfill Prev Device Overfill Drop Tube Valve 4/21/2026 4/21/2029
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 4/21/2026 4/21/2029
Leak Detect - Piping Sump Sensor 4/21/2026 4/21/2027
Spill Contain Device Single Wall Spill Bucket 4/21/2026 4/21/2029
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 4/21/2026



Tank Number 6

Capacity: 550 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 12/11/1996
OSFM First Notify Date: 10/17/1996 Abandoned Material:
Current Age: 9 Abandoned Date:
Install Date: 1/1/1987 Red Tag Issue Date:
Last Used Date: 12/1/1996 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/10/2023 5/10/2026
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found