Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2018005
Status: Active
Facility Name: KSK Inc., II
Address: 2004 Martin Luthern King Jr. Drive North Chicago, IL 60064
County: Lake
Property Parcel: 12-05-125-046
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000734
Green Tag Issue Date: 3/19/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: KSK, Inc. II
Owner Address: 2004 Martin Luther King, Jr. Drive North Chicago, IL 60064
Owner Status: Current Owner
Purchase Date: 1/5/2018
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 10/1/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039046 KSK, Inc. II Current Owner 1/5/2018
U0020137 Marlo Enterprise Former Owner 7/13/1992
U0011329 Olson Oil Company, Inc. Former Owner 12/31/1967
U0029825 Jay Properties & Management, Inc. Former Owner
U0011330 Petroleum Properties Partnership Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260212 (Pending)    Issue Date: 1/29/2026    Expiration Date: 3/30/2026    View NOV Form

Tanks Violations
Facility Fire Extinguishers - Past due for annual testing - Last tested July 2024

NOV Number: E0020260215 (Pending)    Issue Date: 1/29/2026    Expiration Date: 3/30/2026    View NOV Form

Tanks Violations
Facility Facility Operation and Maintenance Plan not completed or available. - Adopt and implement a written operations and maintenance plan, signed by both the owner and either a Class A or Class B Operator designated for the UST facility An Operations & Maintenance template is available at www.sfm.illinois.gov to download and complete O & M template and maintain completed form on site.
3 Install or replace lockable fill pipe caps.
1, 2, 3 Miscellaneous - Fill pipe containment cover shall be identified by color code or labeling to indicate the product contained in the tank. (Per 41 Ill Admin code 175.445.d)
3 Miscellaneous - Mechanical line leak detector detached.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures plan shall be maintained on site for viewing and reference as necessary (See Operator Training Rules 176.645). The emergency plan template is available on the OSFM website.
Facility Missing list of designated Class A/B & C Operators
3 Precision line test required. - Precision line test required due to detached MLLD
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1, 2, 3 Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. - Dispenser 5/6 containment sump(s) contain(s) liquid. Remove liquid and repair containment to prevent further liquid ingress. Must provide documentaion showing repairs completed. (Per 41 Ill Admin code 175.410(h))

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
94-2036 9/7/1994 Removal Log

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 5000 Diesel Fuel Currently in use Federal $0.00
2 8000 Gasoline - Regular Currently in use Federal $0.00
3 5000 Gasoline - Premium Currently in use Federal $0.00
4 550 Heating Oil Removed Federal $0.00 09/07/1994 - REM

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found