| 5, 6 |
Dispensers - hoses cracked, split or worn and require replacement |
| 5 |
Miscellaneous - Tank monitor is showing probe out, repair to clear alarm. 175.630.c2 |
| Facility |
Missing copies of 30 day Walkthrough Inspection Report. |
| Facility |
Missing copies of current testing certificates for operator training - Certificates need to be kept on site |
| Facility |
Missing list of designated Class A/B & C Operators |
| 5 |
Precision tank test required. - Precision tank test is required on tank if you cannot provide 24 months’ worth of tank “PASS” from ATG for regular tank |
| 4, 5, 6 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |