Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2017221
Status: Active
Facility Name: Northlake Marathon
Address: 2 East Lake Street Northlake, IL 60164
County: Cook
Property Parcel: 15-05-101-013-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000033
Green Tag Issue Date: 4/22/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: St. George Petro, LLC
Owner Address: 2 East Lake St. Northlake, IL 60164
Owner Status: Current Owner
Purchase Date: 1/12/2015
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 8/20/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037653 St. George Petro, LLC Current Owner 1/12/2015
U0033172 Northlake Petroleum, Inc., Former Owner 9/1/2005
U0032316 Summit Properties, LLC Former Owner 1/1/2001
U0008879 Land Tr No 2644 Former Owner 12/31/1967
U0027381 LaSalle National Bank Trust #50905 Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260913 (Pending)    Issue Date: 4/7/2026    Expiration Date: 6/6/2026    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
7, 8, 9, 10 Annual leak detection certification not completed (Required annually).
7 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Cannot open lid to access tank top sump, please repair
7, 8, 9, 10 Line interstitial sensor functional test not accomplished (Required annually).
7, 8, 9 Line interstitial sensors have been raised and rendered inoperational. - Under 1/2
7, 8, 9, 10 Mechanical line leak detector requires annual functional test.
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copies of current testing certificates for operator training - Copies need to be kept on site
7, 8, 9, 10 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
7, 8 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
7, 8, 9, 10 Tank interstitial sensor functional test not accomplished (Required annually).

NOV Number: E0020260914 (Pending)    Issue Date: 4/7/2026    Expiration Date: 6/6/2026    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
04-1465 10/22/2004 Removal Log 05342-2004REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
98-2696 Eligible 10/22/1999 11/5/1999 $10,000
19982696 Eligible 9/14/2023 9/22/2023 $10,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/22/2004
OSFM First Notify Date: 4/16/1986 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 1/1/1984 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1984

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/22/2004
OSFM First Notify Date: 4/16/1986 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 1/1/1976 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1976

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/22/2004
OSFM First Notify Date: 4/16/1986 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 1/1/1976 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1976

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 7500 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/22/2004
OSFM First Notify Date: 4/16/1986 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 1/1/1976 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1976

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 1000 Petroleum Use: Consumptive Use on Premises for Heating
Product: Heating Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 10/22/2004
OSFM First Notify Date: 9/22/2004 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1973 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 500 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 10/22/2004
OSFM First Notify Date: 9/22/2004 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1973 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 7

Capacity: 18000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/8/2010 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 11/17/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/17/2006

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/21/2026 5/21/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 5/21/2026 5/21/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/21/2026 5/21/2027
Overfill Prev Device Overfill Drop Tube Valve 4/11/2025 4/11/2028
Piping Flexible Double Wall Total Containment Omniflex II N/A N/A
Piping Single Wall STP/Tanktop Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor 3/26/2025 3/26/2026
Leak Detect - Piping Sump Sensor with positive shutdown 6/5/2025 6/5/2026
Spill Contain Device Single Wall Spill Bucket 4/11/2025 4/11/2028
Tank Composite Double Wall Permatank N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Omniflex II Precision Test (Piping) Pass 2/8/2024



Tank Number 8

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/29/2007 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 11/17/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/17/2006

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/21/2026 5/21/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 5/21/2026 5/21/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/21/2026 5/21/2027
Overfill Prev Device Overfill Drop Tube Valve 5/28/2025 5/28/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor 4/11/2025 4/11/2026
Spill Contain Device Single Wall Spill Bucket 4/11/2025 4/11/2028
Tank Composite Double Wall Permatank N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 2/8/2024



Tank Number 9

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/29/2007 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 11/17/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/17/2006

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/21/2026 5/21/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 5/21/2026 5/21/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/21/2026 5/21/2027
Overfill Prev Device Overfill Drop Tube Valve 4/11/2025 4/11/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Flexible Double Wall Total Containment Omniflex II N/A N/A
Piping Single Wall STP/Tanktop Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor 3/26/2025 3/26/2026
Spill Contain Device Single Wall Spill Bucket 4/11/2025 4/11/2028
Tank Composite Double Wall Permatank N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 2/8/2024
Piping Flexible Double Wall Total Containment Omniflex II Precision Test (Piping) Pass 12/23/2021



Tank Number 10

Capacity: 1000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/8/2010 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 11/17/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/17/2006

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/21/2026 5/21/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 5/21/2026 5/21/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/21/2026 5/21/2027
Overfill Prev Device Overfill Drop Tube Valve 4/11/2025 4/11/2028
Piping Flexible Double Wall Total Containment Omniflex II N/A N/A
Piping Single Wall STP/Tanktop Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor 3/26/2025 3/26/2026
Spill Contain Device Single Wall Spill Bucket 4/11/2025 4/11/2028
Tank Composite Double Wall Permatank N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Omniflex II Precision Test (Piping) Pass 2/8/2024
Tank Composite Double Wall Permatank Precision Test (Tank) Pass 7/21/2023

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/12/2025 8/12/2028
Leak Detect - Piping Sump Sensor 5/21/2026 5/21/2027



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor 5/21/2026 5/21/2027



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor with positive shutdown 5/21/2026 5/21/2027



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor 5/21/2026 5/21/2027



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor 5/21/2026 5/21/2027



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor 5/21/2026 5/21/2027



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/11/2025 4/11/2028
Leak Detect - Piping Sump Sensor 5/21/2026 5/21/2027



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/12/2025 8/12/2028
Leak Detect - Piping Sump Sensor 5/21/2026 5/21/2027

MFD Motorfuel Dispensing Forms

No Forms Found