Notice of Violatlions (Current)
NOV Number:
E0020252941
(Referred to Legal)
Issue Date:
11/4/2025
Expiration Date:
1/3/2026
View NOV Form
| Tanks |
Violations |
| 4, 5, 6 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). - (All Droptubes) |
| 4, 5, 6 |
Triennial spill prevention equipment testing not completed. - (All Spill Buckets) |
NOV Number:
E0020260090
(Pending)
Issue Date:
1/13/2026
Expiration Date:
3/14/2026
View NOV Form
| Tanks |
Violations |
| 4 |
Annual leak detection certification not completed (Required annually). - (ATG Cert.) |
| Facility |
Financial responsibility must be reported yearly - Financial Responsibility form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility |
| 4, 5, 6 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
| 4, 5, 6 |
Tank monitor does not appear to function properly and requires maintenance. - Indicator light(s) on panel of Veeder-Root ATG is/are not functional. Replace as necessary to provide proper operation. (Green light out. All need to be working) |
| 6 |
Tank monitor does not appear to function properly and requires maintenance. - T3 Probe out Alarm and low temp Warning. (Diesel tank is not showing up under inventory. |
NOV Number:
E0020260091
(Pending)
Issue Date:
1/13/2026
Expiration Date:
3/14/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Fire Extinguishers - 2 4A:60BC extinguishers not provided - Provide min of 2 fire extinguishers (4A:60 BC rated), installed to provide access to both employees and customers. |
| Facility |
Fire Extinguishers - Past due for annual testing - Fire extinguishers require annual testing. Have annual testing performed and tag all fire extinguishers accordingly. (April 2024 is the last time it was inspected. ) |