Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2016497
Status: Active
Facility Name: B & R Petroleum, LLC
Address: 4713 W. Elm Street McHenry, IL 60050
County: McHenry
Property Parcel: 09-27-331-020
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001669
Green Tag Issue Date: 3/23/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: B&R Petroleum, LLC
Owner Address: 4713 W. Elm Street McHenry, IL 60050
Owner Status: Current Owner
Purchase Date: 3/21/2025
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 6/8/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/23/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041513 B&R Petroleum, LLC Current Owner 3/21/2025
U0040248 Rahyl Petroleum, LLC Former Owner 4/14/2021
U0038454 V4 Gasoline, Inc. Former Owner 11/23/2016
U0037337 Lehigh Gas Wholesale Services Former Owner 9/27/2016
U0035756 Rameen, Inc. Former Owner 12/31/2009
U0031496 Batul & Shayaan, Inc. Former Owner 8/20/2003
U0031486 The Premcor Refining Group, Inc.. Former Owner 10/24/1994
U0024983 Clark Refining & Marketing, Inc. Former Owner 10/24/1994
U0000651 B.A.P.A., LLC & PT, LLC Former Owner 12/31/1967
U0025164 BAPA, LLC & PT, LLC Former Owner
U0029789 Clark Retail Enterprises, Inc. Former Owner
U0028787 Clark Retail Enterprises, Inc., Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251268 (Pending)    Issue Date: 5/14/2025    Expiration Date: 7/13/2025    View NOV Form

Tanks Violations
Facility Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - Section 175.210g; All dispensing units shall be readily visible from the control station without assistive devices. If view is permanently obstructed, or the dispenser is located so that activity is not readily visible, closed-circuit cameras that provide a view of each side of the dispensing unit and project an image on a screen at least 6 inches in diagonal located at the control station may be used. You may also elect to install an emergency stop switch at least 20 feet but no more than 50 feet from any dispenser with a permanently obstructed view.

NOV Number: E0020251269 (Pending)    Issue Date: 5/14/2025    Expiration Date: 7/13/2025    View NOV Form

Tanks Violations
Facility A/B operator retraining required as a result of issuance of the Notice of Violation - Primary A / B certified operator shall be retrained as a result of this NOV being issued. Go to www.sfm.illinois.gov (UST Operator Training) to find current information regarding Operator Training requirements, including all relevant forms.
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain 2 years on site with other annual testing documentation.
Facility Facility Operation and Maintenance Plan not completed or available. - Adopt and implement a written operations and maintenance plan, signed by both the owner and either a Class A or Class B Operator designated for the UST facility An Operations & Maintenance template is available at www.sfm.illinois.gov to download and complete O & M template and maintain completed form on site.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and 2 years of documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site.
Facility Missing copies of current testing certificates for operator training - Copies of all current Class C testing certificates shall be maintained on file on site.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures plan shall be maintained on site for viewing and reference as necessary (See Operator Training Rules 176.645). The emergency plan template is available on the OSFM website.
Facility Missing list of designated Class A/B & C Operators - A comprehensive list of Class A / B / C Operator(s) shall be maintained on site and must be current.
6, 7, 8 Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. Must maintain 24 months’ worth.
6, 7, 8 Required monthly tank leak test records not available. - Maintain one NORMAL report per TANK, per month, from ATG. Must maintain 24 months’ worth.
6, 7, 8 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Must maintain 2 years of inspection reports.
Facility Submit Notification Form For Ownership Change - Submit OSFM Notification Form showing change in facility ownership. The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of an ownership change.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
15-0372 4/7/2015 Removal Log 00215-2015REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
15-0372 Eligible 4/13/2015 5/19/2015 $5,000
94-2770 Eligible 7/9/2015 7/29/2015 $5,000
20150372 Eligible 1/29/2025 1/30/2025 $5,000 Letter
19942770 Eligible 1/30/2025 1/30/2025 $10,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 4/7/2015
OSFM First Notify Date: 4/6/1986 Abandoned Material:
Current Age: 44 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: 12/9/2013 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 3/20/2014 3/20/2015
Corrosion Prot - Tank Impressed Current Cathodic Protection 3/20/2014 3/20/2015
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 10/24/2013 10/24/2014
Leak Detect - Tank Automatic Tank Gauging Arizona Instruments Encompass
Overfill Prev Device Overfill Drop Tube Valve
Piping Galvanized Steel Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 4/7/2015
OSFM First Notify Date: 4/6/1986 Abandoned Material:
Current Age: 44 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: 12/9/2013 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 3/20/2014 3/20/2015
Corrosion Prot - Tank Impressed Current Cathodic Protection 3/20/2014 3/20/2015
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 10/24/2013 10/24/2014
Leak Detect - Tank Automatic Tank Gauging Arizona Instruments Encompass
Overfill Prev Device Overfill Drop Tube Valve
Piping Galvanized Steel Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 4000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 4/7/2015
OSFM First Notify Date: 4/6/1986 Abandoned Material:
Current Age: 44 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: 12/9/2013 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 3/20/2014 3/20/2015
Corrosion Prot - Tank Impressed Current Cathodic Protection 3/20/2014 3/20/2015
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 10/24/2013 10/24/2014
Leak Detect - Tank Automatic Tank Gauging Arizona Instruments Encompass
Overfill Prev Device Overfill Drop Tube Valve
Piping Galvanized Steel Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 550 Petroleum Use:
Product: Kerosene CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/1/1989
OSFM First Notify Date: 4/6/1986 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 4/7/2015
OSFM First Notify Date: 4/6/1986 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: 1/1/1986 Red Tag Issue Date:
Last Used Date: 12/9/2013 Fee Due: $0.00
Product Date: 1/1/1986

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 3/20/2014 3/20/2015
Corrosion Prot - Tank Impressed Current Cathodic Protection 3/20/2014 3/20/2015
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 10/24/2013 10/24/2014
Leak Detect - Tank Automatic Tank Gauging Arizona Instruments Encompass
Overfill Prev Device Overfill Drop Tube Valve
Piping Galvanized Steel Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/15/2015 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 4/15/2015 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/7/2015

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/24/2025 3/24/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/24/2025 3/24/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/24/2025 3/24/2026
Manway At Grade Accessible Manway Accessible at Grade N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 6/20/2025 6/20/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 6/20/2025 6/20/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/24/2025 3/24/2026
Spill Contain Device Single Wall Spill Bucket 6/20/2025 6/20/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 3/24/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 3/24/2025



Tank Number 7

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/15/2015 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 4/15/2015 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/7/2015

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/24/2025 3/24/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/24/2025 3/24/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/24/2025 3/24/2026
Manway At Grade Accessible Manway Accessible at Grade N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 6/1/2022 6/1/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 6/20/2025 6/20/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/24/2025 3/24/2026
Spill Contain Device Single Wall Spill Bucket 6/20/2025 6/20/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 3/24/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 3/24/2025



Tank Number 8

Capacity: 4000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/15/2015 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 4/15/2015 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/7/2015

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/24/2025 3/24/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/24/2025 3/24/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/24/2025 3/24/2026
Manway At Grade Accessible Manway Accessible at Grade N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 6/20/2025 6/20/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 6/20/2025 6/20/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/24/2025 3/24/2026
Spill Contain Device Single Wall Spill Bucket 6/20/2025 6/20/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 3/24/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 3/24/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/20/2025 6/20/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/24/2025 3/24/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/20/2025 6/20/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/24/2025 3/24/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/20/2025 6/20/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/24/2025 3/24/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/20/2025 6/20/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/24/2025 3/24/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/20/2025 6/20/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/24/2025 3/24/2026

MFD Motorfuel Dispensing Forms