Notice of Violatlions (Current)
NOV Number:
E0020251268
(Referred to Legal)
Issue Date:
5/14/2025
Expiration Date:
7/13/2025
View NOV Form
Tanks |
Violations |
Facility |
Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - Section 175.210g; All dispensing units shall be readily visible from the control station without assistive devices. If view is permanently obstructed, or the dispenser is located so that activity is not readily visible, closed-circuit cameras that provide a view of each side of the dispensing unit and project an image on a screen at least 6 inches in diagonal located at the control station may be used. You may also elect to install an emergency stop switch at least 20 feet but no more than 50 feet from any dispenser with a permanently obstructed view. |
NOV Number:
E0020251977
(Pending)
Issue Date:
8/6/2025
Expiration Date:
10/5/2025
View NOV Form
Tanks |
Violations |
7 |
Drop tube valve or overfill alarm failed inspection. Repair or replace equipment. - Triennial inspection/testing of overfill device (drop tube valve or overfill alarm) failed. Repair/replace as necessary; device(s) shall be retested with passing results and uploaded to OSFM website. |
Facility |
Due to outstanding Motor Fuel Dispensing violation(s) at this facility, after 60 days from the issuance date of this Notice of Violation, and in the absence of full compliance, all tanks shall be red tagged. |