Notice of Violatlions (Current)
NOV Number:
E0020260593
(Pending)
Issue Date:
3/9/2026
Expiration Date:
5/8/2026
View NOV Form
| Tanks |
Violations |
| 5, 7 |
Line leak detection equipment in alarm or failed test, must repair or replace. - s4: (REG UNLD EAST FILL) fuel alarm
s6: (V-POWER FILL) water warning. |
| 5, 7 |
Open electrical conduit or junction boxes. - Conduits inside fill sumps have degraded and broken. Wiring is exposed. |
| 5, 6, 7 |
Verify and test piping sump sensor for positive shutdown - Verify if dispenser sump sensors are stand-alone. |
| 5, 7 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Tanktop sumps contain ~4" of liquid in the corner of the sump. Remove liquid. |